User guide

4-2 Basic Settings and Advanced Settings
4-35
IL-E
4
Setting Various Functions
Laser emission stop input
The laser emission remains interrupted while the laser emission stop input is ON. The laser
emission indicator on the sensor amplifier lights off while the laser emission is stopped.
"Amplifier control unit" (page 1-6)
Timing chart
Minimum Input Time
ON time: 2 ms
OFF time: 2 ms
Set whether to switch the bank with the amplifier buttons or with external inputs.
* If switching with buttons is selected, the bank can be switched only with the buttons.
If switching with external input is selected, the bank can be switched only from the
external input cable.
Reference
Measurements are disabled while the laser emission is stopped. R.V. is
determined by the alarm process.
“2 Display Screen and Output” (page A-8)
Max. 20 ms Max. 20 ms
Min. 20 ms
ON
OFF
Laser emission
stop input
Laser being transmitted
Laser being transmitted
Laser emission being stopped
12. Bank Switching Method
DP-
Setting Description
Default
value
Switching with buttons
The banks are switched by operating the amplifier buttons.
c
Switching with external
input
The banks are switched only by turning ON/OFF the bank
A input or bank B input set in "11. External input".