Instruction Manual
5-6
- IV Series User’s Manual (Field Network) -
Data I/O communication setting method
PLC settings
You can set the following settings for the PLC: 
(1) 
Establish a real-time communication for setting up the data I/O communication.
(2) 
Se the I/O device to be used for the data I/O communication.
For details of the setting, Refer to the instruction manual of each PLC. 
Establishing the data I/O communication
To start a data I/O communication, you need to create a communication path called AR (Application 
Relation) and establish a real-time communication between the I/O controller and the I/O device . When 
you create the AR, separate communication channels for data I/O and record data communications will be 
set up. These communication channels are called CR (Communication Relation). 
The communication is started in the following procedure: 
(1)  The I/O controller requests an AR connection to the I/O device. 
(2)  A response is returned from the I/O device, establishing a real-time communication.
(3) A connection will open if no error is encountered in the compatibility check. 
(1) Requesting an AR connection
(2) Establishing a real-time communication
I/O device
PROFINET 
communication
I/O Controller
Communication settings for the data I/O communication, such as SendCycle (communication cycle) and 
the data size, will be congured on the I/O controller side. 
In a network with many connected devices (including the PROFINET devices), a network delay and/
or packet loss may occur when there is a heavy load on the network. Conduct a thorough verication 
before the operation. 
5
Data I/O communication