Data I/O communication setting method
11  
Open [PROFINET IO] - [Additional Field 
Devices] - [Sensors] - [Keyence Vision 
Sensors] from [Hardware Catalog] in the 
[HW Cong] window, and then drag & 
drop [IV-xxxx] onto [PROFINET-IO-System] 
in the Station Window. 
The IV series will be added to the Station 
Window; and all modules available for the IV 
series will be added automatically. 
If [PROFINET-IO-System] is not displayed 
on the Station Window, right-click [PN-IO] 
of the CPU and select [Insert PROFINET IO 
System]. 
12 
Double-click the IV series icon in the [HW 
Cong] window. 
The [Properties - IV series] window will appear. 
13 
Enter the same character string as the 
PROFINET device name of the IV series to 
be connected into the [Device name] eld. 
14 
Click the [Ethernet] button. 
The [Properties - Ethernet interface IV series] 
window will appear. 
15 
Enter the IP address for the IV series to be 
connected into the [IP address] eld. 
16 
Click the [OK] button to return to the [HW 
cong] window. 
5
Data I/O communication