96M11802 *96M11802-1* Super-small Programmable Logic Controller with Built-in Display KV Series Expansion Unit Instruction Manual
CONTENTS Safety Precautions ....................................................................................... 1 Precautions on Regulations and Standards ........................................................ 2 Inspection and Maintenance ........................................................................ 3 Specifications ............................................................................................... 4 KV-E4X/E8X/E16X (Expansion input unit) ........................................
SAFETY PRECAUTIONS This instruction manual describes the operation and function of the KV. Read this manual carefully to ensure safe use and maximum performance from your KV. Symbols The following symbols alert you to important messages. Be sure to read these messages carefully. WARNING Failure to follow instruction may lead to injury. (electric shock, burn, etc.) CAUTION Failure to follow instructions may lead to product damage. Note: Provides additional information on proper operation.
PRECAUTIONS ON REGULATIONS AND STANDARDS ■ CE Marking Keyence Corporation has confirmed that this product complies with the essential requirements of the applicable EC Directive, based on the following specifications. Be sure to consider the following specifications when using this product in the Member State of European Union.
INSPECTION AND MAINTENANCE Inspection While basic units and other units have been used for a long period of time, the connector connection area may become loose, the battery may wear out, or another nonconformity may occur in operation. To avoid any nonconformities, inspect the basic units, other units, and the wiring periodically. The major inspection items are as follows. • Check to ensure that the connector is not disconnected or loose. • Check to ensure that terminals on terminal plates are not loose.
SPECIFICATIONS Item Specifications AC power type DC power type Power supply type KV-10AR/AT(P) KV-16AR/AT(P) KV-10DR/DT(P) KV-16DR/DT(P) Basic Input supply voltage units Allowable instantaneous time KV-24AR/AT(P) KV-40AR/AT(P) KV-24DR/DT(P) KV-40DR/DT(P) 100 to 240 V AC (± 10%) 24 V DC (+10%, -20%) Less than 40 ms Less than 2 ms KV-10AR/DR: 100 mA or less Basic units Internal current consumption (converted into Expansion 24 V DC value) units Others Surrounding air temperature Relative humi
KV-E4X/E8X/E16X (EXPANSION INPUT UNIT) Part names and functions 1. Input terminal block C1 1 0 3 2 0 IN 2. Input indicator lamps 1 3. READY/ERROR indicator lamp 4. Expansion cable 5. Connector (provided on side) EYENCE ch KV-E4X READY /ERROR 2 V2 V1 3 2. Input indicator lamps V4 V3 V5 IN 1. Input terminal block No.
Terminal layout drawings and input circuit diagrams KV-E4X (4-point expansion input unit) ■ Terminal layout drawing ■ Input circuit diagram Photocoupler insulation 510 Ω C1 C1 1 • V1 to V5 are shortcircuited inside (so they can be used as a relay terminal block). 3 0 Internal circuit Three-wire tipe 4.
0 to 3 4 to 7 8 to 11 12 to 15 C1 C2 C3 C4 9 11 4.
KV-E4R/E4T/E8R/E8T(P)/E16R/E16T(P) (EXPANSION OUTPUT UNIT) Part names and functions 1. Output terminal block C1 1 0 3 2 0 OUT 2. Output indicator lamps 1 3. READY/ERROR indicator lamp 4. Expansion cable 5. Connector (provided on side) EYENCE ch KV-E4R READY /ERROR 2 V2 V1 3 2. Output indicator lamps V4 V3 V5 OUT 1. Output terminal block No.
Output specifications KV-E4R/E8R/E16R (Relay output type) Model Unit type KV-E4R KV-E8R KV-E16R 4-point relay output 8-point relay output 16-point relay output 4 8 16 Number of outputs Output type Relay External connection method Rated load voltage Terminal plate 250 V AC/30 V DC Rated output current 2 A (inductive load) 2A/point (inductive load) ON resistance 4 A (resistive load) 4 A/point (resistive load) 4A/common 50 mΩ or less Common method 4 points/common Rising operation time (
KV-E8R (8-point expansion output unit (relay output type)) ■ Terminal layout drawing 1 3 0 2 V2 V1 C1 1 3 V2 0 0 to 3 4 to 7 Internal circuit C1 ■ Output circuit diagram 2 C1 C2 V1 • C1 and C2 are each independent. • V1 to V2 and V3 to V4 are short-circuited inside (so they can be used as relay terminal plates).
Output specifications KV-E4T/E8T(P)/E16T(P) (Transistor output type(NPN/PNP)) Model KV-E4T Unit type KV-E8T(P) 4-point transistor output Number of outputs 4 8 Output type 16 Transistor (NPN)/(PNP) External connection method Terminal plate Rated load voltage 30 V DC Rated output current 0.5 A/point(NPN), 0.3 A/point(PNP) Leak current in OFF status 100 µA or less Residual voltage in ON status 0.
KV-E8T(P) (8-point expansion output unit (transistor output type)) ■ Terminal layout drawing C1 1 0 3 2 ■ Output circuit diagram *1 V2 NPN Insultating power supply V1 C1 1 0 3 2 0 to 7 Internal circuit V2 V1 C1 C2 PNP 4 C2 6 V3 5 7 V4 4 C2 V3 6 C2 C1 Internal circuit Internal circuit 0 to 7 Insultating power supply 7 5 V4 • V1 to V2 and V3 to V4 are short-circuited inside (so they can be used as relay terminal plates).
KV-E4XR/E4XT(P) (EXPANSION I/O UNIT) Part names and functions 1. Input terminal block C1 X3 X1 X0 V2 X2 V1 IN 3. Input indicator lamps 0 1 2 3 4. READY/ERROR indicator lamp 6. Expansion cable 5. Output indicator lamps EYENCE ch KV-E4XR 7. Connector READY /ERROR 0 Y0 C2 1 Y2 Y1 2 3 V3 Y3 V4 OUT 2. Output terminal block No.
Output specifications KV-E4XR (Relay output type) Item Specifications Output type Relay External connection method Terminal plate Rated load voltage 250 V AC/30 V DC Rated output current 2 A (inductive load) 2A/point (inductive load) ON resistance 4 A(resistive load) 4A/point (resistive load) 4A/common 50 mΩ or less Common method 4 points/common Rising operation time (OFF ➞ ON) 10 ms or less Falling operation time (ON ➞ OFF) 10 ms or less Relay service life Electrical: 100,000 times o
KV-E4XT(P) (Transistor output type) Item Specifications Output type Transistor (NPN)/(PNP) External connection method Terminal plate Rated load voltage 30 V DC Rated output current 0.5 A/point (NPN), 0.3 A/point (PNP) Leak current in OFF status 100 µA or less Residual voltage in ON status 0.
INSTALLATION ENVIRONMENT • Locations exposed to direct sunlight • Locations whose ambient temperature is outside the allowable range of 0 to +50°C (32 to 122°F) • Locations whose ambient humidity is outside the allowable range of 35 to 85% RH • Locations subject to drastic temperature change where condensation may occur • Locations with corrosive or flammable gases • Locations with excessive dust, salt, iron powder, or soot • Locations subject to direct vibrations and impacts • Locations subject to splashes
INSTALLATION PROCEDURE This section describes how to attach a connected unit directly to a panel, to a DIN rail, or to a DIN rail with an expansion unit spacer. ■ Attaching a unit directly to a panel Attach a metal fixture for screw tightening to a KV Series basic unit with set screws. Then, attach the basic unit with a metal fixture directly to the panel.
■ Attaching the spacer to the expansion unit Insert the upper claw of the spacer into the upper groove of the expansion unit and press the lower claw of the spacer until you hear a click. ■ Attaching the spacer to the DIN rail Lower the sliding tabs at both sides of the spacer and insert the upper claw of the spacer into the upper side of the DIN rail. Press the spacer onto the DIN rail and raise the sliding tabs until you hear a click.
■ When I/O signal lines cannot be separated from the wiring for power In such a case, perform grounding on the KV side using batch-shielded cables. (In some environments, grounding should be performed on the reverse side of the KV.) KV Shielded cable Sensor Input RL Output 24 V DC Ground ■ Terminal The terminal screws used are M3. When performing wiring with crimp-style terminals, use the following ones. 6.0 maximum 6.
Note 1: Use a load coil whose rating is less than the contact capacity. Note 2: Use a diode whose peak inverse voltage is 10 times or more the circuit voltage and whose forward current is not less than the load current. Note 3: Individually attach diodes, varistors, and CR circuits directly to the relay coil terminal. CONNECTING KV SERIES EXPANSION UNITS • Connect a basic unit and an expansion unit with an expansion cable. • An expansion cable approximately 60 mm long is provided as standard.
CAUTION Be sure to turn off the power before connecting or disconnecting expansion cables. If they are connected or disconnected while the power is on, the units may be damaged or fail. Note: Keep noise sources such as power cables and electromagnetic switches away from expansion cables (300 mm) as much as possible. Connection methods 1. Peel off the tape stuck to the right side of the basic unit. 2. Connect an expansion cable to the connector.
DIMENSIONS ■ KV-E4X/E8X/E16X (Expansion inut unit) Front view (KV-E4X) Front view (KV-E8X) Front view (KV-E16X) Side view 35.4 90 38 45 4 65 4 43.5 ■ KV-E4R/E4T/E8R/E8T(P)/E16R/E16T(P) (Expansion output unit) Front view (KV-E4x) Front view (KV-E8x) Front view (KV-E16x) Side view 35.4 90 38 45 4 65 4 43.5 ■ KV-E4XR/E4XT(P) (Expansion I/O unit) Side view Front view 35.4 90 4 45 4 43.
METAL FIXTURE FOR SCREW TIGHTENING ■ KV-E4R/E4T/E8R/E8T(P)/E16R/E16T(P) (Expansion output unit) ■ KV-E4X/E8X/R16X (Expansion I/O unit) ■ KV-E4XR/E4XT(P) (Expansion I/O unit) OP-35349 4-ø5.0 (mounting hole) Main unit mounting hole* (2 positions) 99 111 25 38 t=2 * Two M3.5 countersunk-head screws are included for mounting the main unit.
WARRANTIES AND DISCLAIMERS KEYENCE, at its sole option, will refund, repair or replace at no charge any defective Products within 1 year from the date of shipment. Unless stated otherwise herein, the Products should not be used internally in humans, for human transportation, as safety devices or fail-safe systems.