Instruction Manual

7-18
PLC Link
7
7-3 Settings
Omron SYSMAC Series Settings
N-410 settings
CJ Series, CS Series (CPU mounted board)
CS1W-SCB21/41 (Communication port)
CS1W-SCU21 (Communication unit)
(Dipswitch)
(PC system settings)
m=D30000 +100 x unit number
* The default values are baud rate = 9600 bit/s, data bits = 7, parity = even and stop bit length =
2. To use any settings besides these, set "bit" to "1" and then change the settings to suit your
needs.
Item Specification
PLC type selection Omron SYSMAC Series
Station number 0
Baud rate 9600 bit/s
Data bits 7 bit
Parity Even
Stop bit length 2 bit
SW No. Setting Description
5OFF
Communication port/
Clear communication conditions
CPU mounted
RS-232C Port
Communication
port
Communication
unit
Bit Setting item DM value
Channel 160
Port 1: DM32000
Port 2: DM32010
Port 1: m
Port 2: m+10
00 to 01
Parity
00: Even
0000
2
Stop bit
0: 2 bit
3
Data bits
0: 7 bit
8 to 11
Communication
Mode
00: Host link
15
Optional settings
0: Default (*)
Channel 161
Port 1: DM32001
Port 2: DM32011
Port 1: m
Port 2: m+10
00 to 07
Communication
speed
06: 9600 bit/s
0006