Instruction Manual

13
E SK-1000 IM
Peak hold
The maximum value of the specified period (sampling period) is held as a
judgment value (P.V.).
z When "Level" is set for "7. Timing input" (page 14)
When the timing input is turned ON, the maximum value of the internal
measurement value (R.V.) during the sampling period is held as the judgment
value (P.V.). When the timing input is turned OFF, the next sampling period begins.
z When "Edge" is set for "7. Timing input" (page 14)
When the timing input is turned ON, the maximum value of the internal
measurement value (R.V.) during the sampling period is held as the judgment
value (P.V.). Also, when the timing input is turned ON, the next sampling period
begins.
Bottom hold
The minimum value of the specified period (sampling period) is held as a
judgment value (P.V.).
z When "Level" is set for "7. Timing input" (page 14)
When the timing input is turned ON, the minimum value of the internal
measurement value (R.V.) during the sampling period is held as the judgment
value (P.V.). When the timing input is turned OFF, the next sampling period begins.
z When "Edge" is set for "7. Timing input" (page 14)
When the timing input is turned ON, the minimum value of the internal
measurement value (R.V.) during the sampling period is held as the judgment
value (P.V.). Also, when the timing input is turned ON, the next sampling period
begins.
P-H
Display value
Time
Timing Input
Sampling period Sampling periodSampling period
ON
OFF
Power ON or
Reset input *
1
After the power is turned on or reset is input, the judgment value (P.V.) is
[- - - - -] until the timing input is first turned ON.
Judgment value (P.V.)
Internal measurement value (R.V.)*
2
Display value
Time
Timing Input
Sampling period Sampling periodSampling period
ON
OFF
Power ON or
Reset input *
1
After the power is turned on or reset is input, the judgment value (P.V.) is
[- - - - -] until the timing input is first turned ON.
Judgment value (P.V.)
Internal measurement value (R.V.)*
2
b-H
Display value
Time
Timing Input
Sampling period Sampling periodSampling period
ON
OFF
Power ON or
Reset input *
1
After the power is turned on or reset is input, the judgment value (P.V.) is
[- - - - -] until the timing input is first turned ON.
Judgment value (P.V.)
Internal measurement value (R.V.)*
2
Display value
Time
Timing Input
Sampling period Sampling period Sampling period
ON
OFF
Power ON or
Reset input *
1
After the power is turned on or reset is input, the judgment value (P.V.) is
[- - - - -] until the timing input is first turned ON.
Judgment value (P.V.)
Internal measurement value (R.V.)*
2
Absolute value hold
Within the specified period (sampling period), the absolute value of the maximum
value of the measured value is held as the judgment value (P.V.).
z When "Level" is set for "7. Timing input" (page 14)
When the timing input is turned ON, the maximum absolute value of the internal
measurement value (R.V.) during the sampling period is held as the judgment
value (P.V.). When the timing input is turned OFF, the next sampling period begins.
z When "Edge" is set for "7. Timing input" (page 14)
When the timing input is turned ON, the maximum absolute value of the internal
measurement value (R.V.) during the sampling period is held as the judgment
value (P.V.). Also, when the timing input is turned ON, the next sampling period
begins.
Auto peak hold
Until the reset input is turned ON, the maximum value is held as the judgment
value (P.V.). External input is not necessary.
Auto bottom hold
Until the reset input is turned ON, the minimum value is held as the judgment
value (P.V.). External input is not necessary.
A-H
Absolute value-hold value
Display value
Time
Timing Input
ON
0
OFF
Power ON or
Reset input
Sampling period Sampling period Sampling period
After the power is turned on or reset is input, the judgment value (P.V.) is
[- - - - -] until the timing input is first turned ON.
Measurement value
Absolute value-hold value
Display value
Time
Timing Input
ON
OFF
Power ON or
Reset input
Sampling period Sampling period
Sampling period
After the power is turned on or reset is input, the judgment value (P.V.) is
[- - - - -] until the timing input is first turned ON.
Measurement value
Auto.P
Auto peak hold value
Display value
Time
Timing Input
ON
OFF
Reset input
ON
OFF
Measurement value
Auto.b
Auto bottom hold value
Display value
Time
Timing Input
ON
OFF
Reset input
ON
OFF
Measurement value