Simulation Mode
You can use this function to check that the I/O control cable has been wired
correctly.
Main screen
1 On the main screen, while pressing the
[MODE] button, press the W button five times.
[51.out] is displayed on the main display (upper
level).
While pressing
the [MODE]
button, press the
W button five
times.
2 Use the S/T buttons to display the signal that
you want to output in the sub display (lower
level). The signal will be output when it is
displayed. Press the [MODE] button to
proceed to the next step.
[MODE] button
3 When you turn ON external input 1 to external
input 4, the corresponding part of the display
will change from [_] to [o].
From the right, the parts correspond to external
inputs 1, 2, 3, and 4.
Press the [MODE] button to proceed to the next step.
(Example) [___o] indicates that external input 1 is
on.
[o_o_] indicates that external inputs 2
and 4 are on.
[MODE] button
4 The upper limit, middle value, and lower limit
of the analog output are generated. This is not
displayed when the analog output is turned
OFF. Press the [MODE] button to proceed to
the next step.
(Example) When the analog output setting is 0 to 5 V
5 V is output for Hi, 2.5 V is output for Mid,
0 V is output for Lo, and 5.5 V is output for
Err.
[MODE] button
5 [END] is displayed on the sub display (lower
level). Press the [MODE] button to complete
the procedure and return to the main screen.
HOLD
HI
V
kV
ALARM
BANK
ZERO SHIFT
TIMING
TEMP %RH
HI LO R.V.
0
1
2
3
LO
GO
off
51.out
Setting value Description
OFF No signal is output.
HI The HI signal is output.
GO The GO signal is output.
LO The LO signal is output.
ALM The alarm signal is output.
----
52.in
Hi
53.AnG
Setting
value
Description
Hi
The upper limit of the analog output is
generated.
Mid
The middle value of the analog output is
generated.
Lo
The lower limit of the analog output is
generated.
Err
The output value when an error occurs is
output.
HOLD
HI
V
kV
ALARM
BANK
ZERO SHIFT
TIMING
TEMP %RH
HI LO R.V.
0
1
2
3
LO
GO
Return to the
main screen.
5. Specifications
This chapter describes the specifications, circuit diagrams, and dimensions of the
SK Series.
Specifications
Sensor head
*1 Even in the measurement area, if the distance to the detection target is smaller than the
reference distance, measurement cannot be performed up to the upper limit of the
measurement range.
*2 When measured an average of 256 times, this value is ±100 V or less in high-precision
mode and ±1 kV or less in wide-range mode, and ±10% (indicated value) in other ranges.
*3 The measurement accuracy range is ± 30 kV.
*4 At 25°C and with a humidity of 50%RH
*5 OP-87934 is necessary.
*6 This is when ±100 V or less, and ±10% (indicated value) in other ranges.
Sensor amplifier
*1 Select one from ±5 V, 1-5 V, 0-5 V, 4-20 mA.
*2 The four external input wires are assigned to arbitrary inputs.
Rated novoltage input: ON voltage of 2 V or less, OFF current of 0.02 mA or less.
Rated voltage input: max. input rating of 30 V or less, ON voltage of 7.5 V or more, OFF
current of 0.05 mA or less.
*3 Rated NPN open-collector output: max. 50 mA/ch (20 mA/ch when expansion units are
connected), 30 V or less, residual voltage of 1 V or less (1.5 V or less when five or more
expansion units are connected).
Rated PNP open-collector output: max. 50 mA/ch (20 mA/ch when expansion units are
connected), supply voltage or less, residual voltage of 2 V or less (2.5 V or less when five or
more expansion units are connected).
*4 Power supply voltage of 20-30 V when five or more expansion units are connected.
*5 Max. 11.3 W when eight units and the DL Series are connected.
Model SK-050
Electrification
potential
measurement
Measurement mode High precision Wide range
Reference distance for
measurement
25 mm 100 mm
Measurement distance 5 to 50 mm 60 to 120 mm
Measurement range
*1
±2 kV ±50 kV
Measurement accuracy
*2
±10 V ±100 V
*3
Sampling time Approx. 1.4 ms
Temperature
measurement
Measurement range 0 to 50°C
Measurement accuracy
*4
±1°C
Minimum display unit 0.1°C
Sampling time 1 s
Humidity
measurement
Measurement range 10 to 85% RH
Measurement accuracy
*4
±5% RH
Minimum display unit 0.1% RH
Sampling time 1 s
Ion balance
measurement
mode
*5
Ion balance measurement
range
±1 kV
Measurement accuracy
*6
±10 V
Minimum display unit 1 V
Environmental
resistance
Ambient temperature 0 to 50°C (no freezing and no condensation)
Ambient humidity 10 to 85%RH (no condensation)
Materials Main body case: PC, metal part: SUS, cable: PVC
Weight Approx. 35 g
Model SK-1000 SK-1050
Type Mounting DIN rail.
Main unit/expansion unit Main unit Expansion unit
Display
Minimum display unit 0.001 kV
Display range ±99.999 kV to 99 kV (Four-stage selection possible)
Analog voltage output
*1
±5 V, 1-5 V, 0-5 V,
Load resistance: 100Ω
Analog current output
*1
4 to 20 mA
max. load resistance 350Ω
Control
input
*2
Zero shift input
No-voltage input
Timing input
Reset input
Bank input
Control
output
*3
Judgment output
Open-collector output
(NPN/PNP switchable; NO/NC switchable)
Alarm output Open-collector output (NPN/PNP switchable, N.C.)
Power
supply
Supply voltage
*4
10 to 30 VDC including
10% ripple (P-P)
Supplied from the main
unit.
Current consumption
(Excluding the load
current of each output.)
*5
1650 mW or less
(at 30 V, 55 mA max)
1170 mW or less
(at 30 V, 39 mA max)
Environmental
resistance
Ambient temperature 0 to 50°C (no freezing and no condensation)
Ambient humidity 10 to 85%RH (no condensation)
Materials
Main body case / front cover: PC, key top: POM,
cable: PVC
Weight (Including accessories) Approx. 150g Approx. 140g