2-11 Temporary Suspension of Safety Function
2-33
Functions and Features
2
SL-V-M-NO2-E
The conditions related to muting can be changed through the special procedure on the SL-V or through
the SL-VH1S.
(X: available -: not available)
If you choose these options according to your machine application, password setting and/or password
input is required as a special procedure.
The password can be set on the SL-V main unit or through the configuration software SL-VH1S.
The users who intend to use these options mentioned above from 1 to 3, 5 and 6 have to
perform the risk assessment based on their machine application.
Muted condition is terminated approx. 5 minutes later when the time between muting inputs exceeds 3
seconds, even if "Not specified" is selected for both maximum muting period of time and time between
muting inputs.
Password must be secured because the password is necessary to change the condition for initiation
and/or termination of muting or change these conditions back to the default.
The override conditions cannot be changed. See "Override function" (page 2-45)
Procedure for configuration through the SL-VH1S
Refer to "SL-VH1S User’s Manual".
Changing configuration of the muting function
Item option
availability
SL-V SL-VH1S
Changing of the
conditions for initiation
of muting
1. Time period specification of muting inputs
Time period specification of 0.04s to 3s between
muting input 1 and muting input 2 can be changed.
The lower limit of 0.04s cannot be changed.
1 second - X
3 seconds (default) X X
10 second - X
30 second - X
Not specified X X
2. Sequence specification of muting inputs
Sequence specification of muting inputs can be
changed. (Default sequence: muting input 1 is first,
muting input 2 is second.)
1 -> 2 fixed (default) X X
Not specified X X
Conditions for
termination of muting
3. Maximum muting period
Maximum muting period of approx. 5 minutes can be
changed.
1 minute - X
5 minutes (default) X X
10 minutes - X
20 minutes - X
Not specified X X
4. Muting lamp error
Sets whether the SL-V goes to the lockout condition when there is a muting
lamp error.
Only warning (default) X X
Lockout X X
5. Muting area configuration - - X
6. Muting bank function
Not apply (default) X X
Apply - X