3-1 Safety Related Configuration
Configuration for safety functions, such as muting or interlock, is possible by clicking on the [Safety-
related Configuration].
* If the time between muting input 1 and 2 is over 3 seconds while both Time between muting inputs and Maximum
muting period are set to Not specified, the maximum muting period will be limited to approximately 5 minutes.
Muting Configuration
Item
Contents of
Configuration
Description
Time between muting inputs* 1 sec / 3 sec (Default) /
10 sec / 30 sec /
Not specified
This will configure the input time period specification
between the muting inputs 1 and 2. (The lower limit
time of 0.04 sec cannot be changed.)
Muting inputs sequence Muting input1 : First /
Muting input2 : Second
(Default) / Not specified
This will configure the limit of the sequence of muting
inputs 1 and 2 getting turned on.
Maximum muting period* 1 min / 5 min (Default) /
10 min / 20 min /
Not specified
This will configure the maximum muting period of one
muting.
Muting Lamp Error Only Warning (Default) This will output state information when a burned out
muting lamp is detected, but it will not lock-out.
Lockout This will output state information when a burned out
muting lamp is detected, and it will also lock-out.
Override Function
Item
Contents of
Configuration
Description
Maximum override period 30 sec / 1 min (Default) /
5 min / 15 min
This will configure the maximum override period.