Instruction Manual
3-1 Safety Related Configuration
3-3
Configuration of Each Function
3
SL-VH1S-NO3-E
Wiring cannot be selected in the interlock configuration when the muting bank function is
enabled.
"3-4 Muting Area" (Page 3-7)
Interlock Configuration
Item
Contents of
Configuration
Description
Interlock Configuration By wiring (Default) Configuration is switched with the wiring.
By PC Software Configuration is switched with the
<SL-V Configurator>.
(When PC
configuration is
selected)
Start
Interlock
Manual start
(Default)
OSSD will be set to OFF when the power is
turned on. The device will start up with reset
input.
Automatic start Starts the device automatically when the
power is turned on.
Restart
Interlock
Manual reset
(Default)
Holds the OSSD OFF state even when the
clear state is established after beam
interruption. The device will start up with reset
input.
Automatic reset Restarts the device automatically when the
clear state is established after beam
interruption.
Note
EDM Function / Adjustment
Item
Contents of
Configuration
Description
EDM apply (Default) / not apply This will configure if the EDM function is to be used or
not.
EDM Time
0.15 sec / 0.3 sec (Default)
/ 0.6 sec / 3 sec
This will configure the time to become EDM error.