Datasheet

06 | Keysight | N3300 Series DC Electronic Loads - Data Sheet
N3302A N3303A N3304A N3304A-J01 Special
order option
N3305A N3306A N3307A
Programming resolution
Constant current mode
0.05/0.5 mA 0.02/0.2 mA 0.1/1 mA 0.1/1 mA 0.1/1 mA 0.2/2 mA 0.05/0.5 mA
Constant voltage mode
0.1/1 mV 0.4/4 mV 0.1/1 mV 0.135/1.35 mV 0.25/2.5 mV 0.1/1 mV 0.25/2.5 mV
Constant resistance mode
0.07/0.7/7/
70 mΩ
0.82/8.2/
82 mΩ
0.035/0.35/
3.5/35 mΩ
0.05/0.5/5/
50 mΩ
0.085/0.85/
8.5/ 85 mΩ
0.0175/0.175/
1.75/17.5 mΩ
0.17/1.7/
17/170 mΩ
Readback resolution
Current
0.05/0.5 mA 0.02/0.2 mA 0.1/1 mA 0.1/1 mA 0.1/1 mA 0.2/2 mA 0.05/0.5 mA
Voltage
0.1/1 mV 0.4/4 mV 0.1/1 mV 0.135/1.35 mV 0.25/2.5 mV 0.1/1 mV 0.25/2.5 mV
Programmable slew rate
1
Current
ranges
Slow band 50025 kA/s 167–8330 A/s 1 k–50 kA/s 1 k–50 kA/s 1 k–50 kA/s 2–100 k A /s 500–25 kA/s
Fast band ≥3 V 50 k–2.5 MA/s 16.7 k–833
kA/s
100 k–5 MA/s 100 k–5 MA/s 100 k–5 MA/s 200 k–10 MA/s 50 k–2.5
MA/s
Fast band <3 V 50 k–250 kA/s 16.7 k83.3
kA/s
100 k500
kA/s
100 k–500 kA/s 100 k–500
kA/s
200 k–1 MA/s 50 k250
kA/s
Voltage
ranges
Slow band 1 k–50 kV/s 4 k–200 kV/s 1 k–50 kV/s 1.33 k–66.6 kV/s 2.5 k–125 kV/s 1 k–50 kV/s 2.5 k–125
kV/s
Fast band ≥3 V 100 k–
500 kV/s
400 k–
2 MV/s
100 k–
500 kV/s
133 k
666 kV/s
250 k–
1.25 MV/s
100 k–
500 kV/s
250 k–
1.25 MV/s
Fast band <3 V 100 k–50 kV/s 400 k200
kV/s
100 k–50 kV/s 133 k–66.6 kV/s 250 k–125
kV/s
100 k–50 kV/s 250 k125
kV/s
Resistance
range 1
Slow band 441125 Ω/s 54013.5 kΩ/s 22–560 Ω/s 30745 Ω/s 551400 Ω/s 11280 Ω/s 110–2800 Ω/s
Fast band ≥3 V 2250–34 kΩ/s 27 k–408 kΩ/s 112017 kΩ/s 1500–22.6 kΩ/s 280042.5
kΩ/s
5608.5 kΩ/s 5600–85
kΩ/s
Fast band <3 V 2250–3.4
kΩ/s
27 k–40.8 kΩ/s 1120–1.7 kΩ/s 1500–2.26 kΩ/s 2800–4.25
kΩ/s
560850 Ω/s 5600–8.5
kΩ/s
Resistance
range 2
Slow band 440 –11.25
kΩ/s
5.4 k–135 kΩ/s 220–5600 Ω/s 3007450 Ω/s 55014 kΩ/s 110–2800 Ω/s 1.1 k–28 kΩ/s
Fast band ≥3 V 22.5 k–
340 kΩ/s
270 k–
4.08 MΩ/s
11.2 k
170 kΩ/s
15 k
226 kΩ/s
28 k–
425 kΩ/s
5600–
85 kΩ/s
56 k–850
kΩ/s
Fast band <3 V 22.5 k–
34 kΩ/s
270 k–
408 kΩ/s
11.2 k
17 kΩ/s
15 k
22.6 kΩ/s
28 k–
42.5 kΩ/s
5600–
8.5 kΩ/s
56 k–
85 kΩ/s
Resistance
range 3
Slow band 4.4 k–
112.5 kΩ/s
54 k–
1.35 MΩ/s
2.2 k–
56 kΩ/s
3 k–
74.5 kΩ/s
5.5 k–
140 kΩ/s
1.1 k
28 kΩ/s
11 k
280 kΩ/s
Fast band ≥3 V 225 k–
3.4 MΩ/s
2.7 M
40.8 MΩ/s
112 k
1.7 MΩ/s
150 k
2.26 MΩ/s
280 k–
4.25 MΩ/s
56 k–
850 kΩ/s
560 k–
8.5 MΩ/s
Fast band <3 V 225 k–
340 kΩ/s
2.7 M
4.08 MΩ/s
112 k
170 kΩ/s
150 k
226 kΩ/s
280 k–
425 kΩ/s
56 k–
85 kΩ/s
560 k–
850 kΩ/s
Resistance
range 4
Slow band 44 k–
1.125 MΩ/s
540 k–
13.5 MΩ/s
22 k–
560 kΩ/s
30 k–
745 kΩ/s
55 k–
1.4 MΩ/s
11 k
280 kΩ/s
110 k
2.8 MΩ/s
Fast band ≥3 V 2.2 M–
34 MΩ/s
27 M–
408 MΩ/s
1.12 M
17 MΩ/s
1.5 M
22.6 MΩ/s
2.8 M–
42.5 MΩ/s
560 k–
8.5 MΩ/s
5.6 M
85 MΩ/s
Fast band <3 V 2.25 M
3.4 MΩ/s
27 M–
40.8 MΩ/s
1.12 M
1.7 MΩ/s
1.5 M
2.26 MΩ/s
2.8 M–
4.25 MΩ/s
560 k–
850 kΩ/s
5.6 M
8.5 MΩ/s
Programmable short
Maximum 66 mΩ 200 mΩ. 33 mΩ 33 mΩ 33 mΩ 17 mΩ 33 mΩ
Typical 40 mΩ 100 mΩ 20 mΩ 20 mΩ 25 mΩ 12 mΩ 20 mΩ
Programmable open
≥ 20 kΩ ≥ 80 kΩ 20 kΩ ≥ 20 kΩ ≥ 20 kΩ ≥ 20 kΩ 80 kΩ
1. Slew rate bands are the ranges of programmable slew rates available. When you program a slew rate value outside the indicated bands, the electronic load will
automatically adjust the slew rate to fit within the band that is closest to the programmed value. It is not necessary to specify the band, only the slew rate itself.
Below 3 volts, the maximum bandwidth of the electronic load is reduced by a factor of ten to one. For example, in the current range for Model N3302A, the maximum
slew rate is specified as 2.5 MA/s, below 3 volts the maximum slew rate would be 250 kA/s. Any slew rate programmed between
2.5 MA/s and 250 kA/s would produce a slew rate of 250 k/s. Slew rates programmed slower than 250 kA/s would still correctly reflect their programmed value. Note
that if you are using transient mode to generate a high frequency pulse train, a reduced slew rate might cause the load to never reach the upper programmed value
before beginning the transition to the lower programmed value. So even though the transient mode is still operational at lower voltages, a fast pulse train with large
transitions may not be achievable.
Supplemental Characteristics
Table A-2 lists the supplemental characteristics, which are not warranted but are descriptions of typical performance determined
either by design or type testing.
Table A-2