Specification Sheet
Kichler.com
0-10V Dimmable Power Supply
9 - VOLTAGE DROP CHARTS
For best performance and lumen output, ensure proper wire gauge is installed to compensate for voltage drop of low voltage circuits.
Determine load size.
Round up to the nearest load.
See the recommended wire gauge to install
to eliminate excess voltage drop.
Determine distance from
Power Supply to load.
Let’s assume the distance is 28ft.
Round up to the nearest length.
5W
0.21A
10W
0.42A
20W
0.83A
30W
1.25A
40W
1.67A
50W
2.08A
60W
2.5A
70W
2.92A
80W
3.33A
90W
3.75A
100W
4.17A
18 AWG 261 ft. 130 ft. 65 ft. 43 ft. 32 ft. 26 ft. 21 ft. 18 ft. 16 ft. 14 ft. 13 ft.
16 AWG 401 ft. 200 ft. 100 ft. 66 ft. 50 ft. 40 ft. 33 ft. 28 ft. 25 ft. 22 ft. 20 ft.
14 AWG 639 ft. 319 ft. 160 ft. 106 ft. 79 ft. 63 ft. 53 ft. 45 ft. 39 ft. 35 ft. 31 ft.
12 AWG 959 ft. 479 ft. 240 ft. 160 ft. 120 ft. 95 ft. 79 ft. 68 ft. 59 ft. 53 ft. 47 ft.
10 AWG 1570 ft. 785 ft. 392 ft. 261 ft. 196 ft. 157 ft. 130 ft. 112 ft. 98 ft. 87 ft. 78 ft.
24V VOLTAGE DROP CHART