Buying Guide

Large Hydronic Heater HL/HLE Series
Engineering Specifications
FT. OF WATER
PRESSURE
DROP @ 2 GPM
120ºF
48ºC
140ºF*
60ºC
160ºF*
71ºC
180ºF
200ºF MAX
82ºC
Motor Hi/Lo Decibels at
3-ft distanceCFM
Hi/Lo: Amps
Hi/Lo: Watts
HL1012 8/11
6000 BTU
4700 BTU
8550 BTU
6200 BTU
11100 BTU
8000 BTU
14800 BTU
11000 BTU
3 watt output
250 / 150CFM
Hi 57/55 dbA
Lo 54/52 dbA
.30 / .29 Amps
36 / 34.8 Watts
HL1012 10/13
7500 BTU
5500 BTU
10000 BTU
8000 BTU
13500 BTU
9750 BTU
16600 BTU
12000 BTU
3 watt output
250 / 150CFM
Hi 57/55 dbA
Lo 54/52 dbA
.30 / .29 Amps
36 / 34.8 Watts
HL1012-11/15
8812 BTU
6600 BTU
11700 BTU
8800 BTU
15500 BTU
11600 BTU
18700 BTU
14000 BTU
5 watt output
375 / 220 CFM
Hi 64/62 dbA
Lo 60/58 dbA
.42 / .38 Amps
50.4 / 45.6 Watts
HL1412-15/20 1.2
10600 BTU
7400 BTU
15500 BTU
11600 BTU
20000 BTU
15000 BTU
26000 BTU
19500 BTU
5 watt output
375 / 220 CFM
Hi 64/62 dbA
Lo 60/58 dbA
.42 / .38 Amps
50.4 / 45.6 Watts
HL1412-20/25 1.2
17000 BTU
13000 BTU
20000 BTU
16800 BTU
24050 BTU
19100 BTU
27250 BTU
22500 BTU
9 watt output
375 / 220 CFM
Hi 64/62 dbA
Lo 60/58 dbA
.42 / .38 Amps
50.4 / 45.6 Watts
HLE 1012-11/15
8812 BTU
6600 BTU
11700 BTU
8800 BTU
15500 BTU
11600 BTU
18700 BTU
14000 BTU
150 to 375 High
150 to 250 Low
Hi 57/55 dbA
Lo 54/52 dbA
.06 / .04 Amps
7.2 / 4.8 Watts
HLE 1412-15/20 1.2
10600 BTU
8812 BTU
15500 BTU
11700 BTU
20000 BTU
15500 BTU
26000 BTU
18700 BTU
150 to 375 High
150 to 250 Low
Hi 63/61 dbA
Lo 54/52 dbA
.09 / .06 Amps
10.8 / 7.2 Watts
HL
HLE
HL / HLE Series Large Hydronic Heater - 6,700 to 27,250 BTU
King’s HL HLE Series large hydronic heater uses the energy from a building’s existing hot water source to offer
efficient, whisper quiet operation and the ability to reduce utility bills with individual room control. By installing hydronic heaters in
every room, you can easily heat only the areas in use and conserve energy. Designed to fit neatly between standard wall studs,
this in-wall heater provides out of the way positioning ideal for use in public areas, corridors, entry ways and large rooms or
hallways. For use in both residential and commercial applications. Provides 6700 to 27,250 BTU heat output. Recommended 17
BTU per square foot for new construction.
.90
.90
.90
.90
Decibels at
3-ft distanceECM Motor
FT. OF WATER
PRESSURE
DROP @ 2 GPM
120ºF
48ºC
140ºF*
60ºC
160ºF*
71ºC
180ºF
82ºC
Progressive
CFM
Model Number Volts Can Size Grill Size
HL & HLE 1012 & 1412 – all versions 120 24¾"h x 14 ¼"w x 4¾"d 26¼"h x 15½"w x ¾"d
Motor: 2 speed shaded pole impedance protected. Permanently lubricated. Bronze
bearings.
Blower: Tangential blower to provide 150 to 375 CFM of air. Quiet operation of
less than 53 dBA weighted scale at high speed. Easily removed for service. Bronze,
not plastic, bearings.
Coils: 1/2" ID Copper tubes with Aluminum fins of no more than 4 fins per inch for
free flow of air and maximum circulation of air and water. Tested at 300 PSI for
leaks. Bleed valve to purge air. Copper tube used in coils is Alloy 122 made to
ASTM B-75 specifications.
Grill: 20 gauge mild Steel, louvered with Nickel-plated grille screws.
Powder-coated in white.
Wall Can: 20 gauge mild Steel, electrogalvanized to resist corrosion. 1/2" knockout
in bottom of can and QuickSet
bend out mounting tabs for fast installation.
Fan Switch: 3 position fan switch High / Off / Low. Rated at 10 Amps with wire
leads and insulated ¼" quick connects.
Terminal Board: All electrical connections will terminate at a phenolic terminal
board with ¼" male brass blades for easy wiring.
Water Connections: 1/2" bare Copper tubes de-burred. Tested at 300 PSI for
leaks. Clean out tubes for water connection.
ECM Motor: We program the motor to start at slowly and quietly at 50% of its
maximum speed. Over a 3 to 5 minute period, if the room is not reaching the
set point it will slowly ramp up to 100% airflow to heat the room. It not only
saves energy but also makes a large output heater have a soft quiet start, yet
can increase to its maximum output and sound level over time while not
disturbing residents.
Approvals: ETL (3131491PRT-001). All King heaters are tested to UL 1995
Standards. Approved for USA and Canada. CSA/C22.2.
Contractor shall supply and install HL/HLE Series hydronic fan heaters manufactured by King Electrical Mfg. Co., Seattle, Washington.
HL 10 12 8/11 AS-FS GW
A B C D E F
A: Series
B: Number of Copper Tubes in Coil
C: 12 - 120V
D: BTU Heat Output
E: Aqua Stat / Fan Switch
F: Grill White or Black color
MODEL
Tangential Blowers
Fast Coil Heating
Quiet Operation
1/2” Trade size copper tubes
Flow-through design
4 or 8 Aluminum fins per inch
Easy motor removal for maintenance
Permanently lubricated motor
Powder-coated white grill
Hi / Off / Lo fan switch
Use HW series thermostats
2-year limited warranty
Hi/Lo: Amps
Hi/Lo: Watts
Energy saver
Energy saver
*most common water temperature range. Coils are made of copper alloy 122 manufactured to ATSM B-75 specifications.
Brazing alloy is AWS-BCUP2 for use with potable water systems. Electrical circuit size: 15 amp maximum.
BTU ratings based on 68˚ entering air. To calculate 1 GPM, multiply by 0.95. To calculate 4 GPM, multiply by 1.05.

Summary of content (1 pages)