DESCRIPTION:
SRP self-regulating pre-assembled heating cables are
designed for a variety of pipe freeze protection as well as roof
and gutter deicing applications. The heat output (wattage)
increases and decreases based on the temperature, so the
cable adjusts automatically to varying climate conditions. This
unique feature ensures maximum energy efficiency by
increasing the heat output only when it is needed. No
thermostat is required.
SRP CABLE FEATURES:
- Rated 6 watts/foot at 40º F, (4º C) for pipe freeze protection.
- Rated 8 watts/foot at 32º F, (0º C) for roof and gutter deicing.
- 30 inch power lead with grounded plug.
- Pre-terminated with 30 inch 120V cord with plug and end
splice.
- Suitable for use on metal and plastic pipes.
- Suitable for metallic and nonmetallic gutters and downspouts.
- Cable will not overheat or burnout when overlapped.
- 16 gauge heating cable bus wire.
- 2 year warranty.
SRP CABLE KIT CONTAINS:
SRP pre-assembled electric heating cable
Roof and gutter caution labels
Pipe trace caution labels
Cable Construction
Model Volts
Pipe
Rating
Deicing
Rating
Length
SRP126
-6 120V
36 watts
48 watts
6 ft.
SRP126
-12 120V
72 watts
96 watts
12 ft.
SRP126
-18 120V
108 watts
144 watts
18 ft.
SRP126
-24 120V
144 watts
192 watts
24 ft.
SRP126
-50 120V
300 watts
400 watts
50 ft.
SRP126
-75 120V
450 watts
600 watts
75 ft.
SRP126
-100 120V
600 watts
800 watts
100 ft.
CAUTION:
1. Heating cables must be installed in compliance with the
national electric code (NEC) in addition to state, provincial and
local codes. Check with your local inspector for specific code
requirements (or regulations or standards) in your area.
2. Save these instructions and transfer them to future owner(s).
3. Never install on pipes that could potentially exceed 150º F,
(65º C).
4. Not for use with an extension cord.
5. Cable should not run through the building walls,
ceilings or floors.
6. For safety, King recommends that all heating cables are placed
on a Ground Fault Equipment Protection (GFEP) circuit.
Consult your local electrical inspector to determine the specific
requirements in your area.
7. Do not cut or alter the length of the cable in any way. Any
alteration may result in electrical shock or fire.
8. Post warning labels supplied with the cable at the power supply
and along the pipe on the outside of the insulation.
9. Do not bend the cable to less than a 1/2” radius.
10.Do not Install cable on shingle roofs in freezing temperatures;
as this may cause damage to the shingles.
11.Cables are intended for freeze protection of water pipes only.
Not intended for use with other liquids or hazardous materials.
12. For installation in accessible areas only.
Installation, Operation and Maintenance Instructions
King Electrical Mfg. Company will repair or replace, without charge to the original owner, any heating cable found to be defective or malfunctioning within the 2 year warranty.
In Case of Product Failure: Contact King Electrical Mfg. Co. at 800.603.5464. The owner will be required to provide, within the designated warranty period, the following
information: model number, date of purchase, and a complete description of the problem encountered with product. Upon receipt of the aforementioned, the company will
reply to the owner within a period not to exceed fifteen (15) working days, and will provide the action to be taken by owner. Terms: This warranty requires the owner or his
agent install the equipment in accordance with the National Electrical Code, any other applicable heating or electrical codes and the manufacturer's installation instructions. It
further requires that reasonable and necessary maintenance be performed on the unit. Failure of proper maintenance by owner will void the warranty in its entirety. The
company is not liable for any actions it deems to be abuse or misuse of the product. The customer shall be responsible for all costs incurred in the removal or reinstallation of
products, including, but not limited to, labor costs, and shipping costs incurred to return products to King Manufacturing. At their discretion, King Manufacturing will decide to
either repair or replace the product, with no charge to the owner, with return freight paid by King. The Company shall not be liable for consequential damages arising with
respect to the product, whether based upon negligence, tort, strict liability or contract. No other written or oral warranty applies, nor any warranties by Representatives,
Dealers, Employees of King or any other person. King Manufacturing can be contacted by phone at 206.762.0400, fax 206.763.7738 or website www.kingelectric.com.The
company's minimum liability shall not in any case exceed the list price for the product claimed to be defective.
Warranty Information:
IMPORTANT: Save These Instructions!
Rev 8.28.12
www.king-electric.com 1

Summary of content (6 pages)