Installation Manual
Kingfisher Company, inc. STAR-ELT Manual
KCi #99420-MAN Rev 0.6 Page 11 of 29
10. Terminal Configurations and Pinouts
Terminal
Description
Usage
TB1-1
Trouble Relay N/O when system normal, closed
when trouble condition occurs
Connect to FACP monitoring
device
TB1-2
Trouble Relay COM
Connect to FACP monitoring
device
TB2-1
Zone 1 Input
Zone 1 dry contact trigger
TB2-2
Zone 1 Input
Zone 1 dry contact trigger
TB2-3
Zone 2 Input
Zone 2 dry contact trigger
TB2-4
Zone 2 Input
Zone 2 dry contact trigger
TB2-5
Zone 3 Input
Zone 3 dry contact trigger
TB2-6
Zone 3 Input
Zone 3 dry contact trigger
TB2-7
Zone 4 Input
Zone 4 dry contact trigger
TB2-8
Zone 4 Input
Zone 4 dry contact trigger
TB3-1
FACP DC Power +
+24VDC from FACP
TB3-2
FACP DC Power -
24VDC COM from FACP
TB3-3
FACP Low Battery +
Low battery dry contact input
from FACP
TB3-4
FACP Low Battery -
Low battery dry contact input
from FACP
TB3-5
FACP Power Fail +
AC Fail dry contact input from
FACP
TB3-6
FACP Power Fail -
AC Fail dry contact input for
FACP
11. Connections
11.1 DC Power
The STAR-ELT can be powered from +24VDC from any FM approved FACP or FM approved
battery backed up auxilliary 24VDC power source by connecting power wiring to TB3-1(+) and
TB3-2 (-). The STAR-ELT provides input power isolation to prevent ground faults occurring on
the FACP powering the unit.
11.2 AC Power (Optional)
The STAR-ELT can be powered directly from the AC line by using an optional power supply,
which also provides support for secondary backup battery power. Either 100 - 120 VAC or 220-
240 VAC nominal line power, with a separate ground wire, is connected to the AC terminal
block on the left hand side of the optional power supply module. The supply is wide-input and
supports both voltage ranges with no configuration changes. Hot, Ground and Neutral wires
should be inserted into the appropriately marked terminals, marked H, G, N and fastened
tightly. Wires can be any size up to 12 AWG.