Installation Manual
Kingfisher Company, inc. STAR-ELT Manual
KCi #99420-MAN Rev 0.6 Page 13 of 29
range that the STAR-ELT will be subjected to. Typically, this is rated from 0°C (32°F) to +50°C
(+120°F). The battery connector J1 is polarized to allow for correct cable orientation.
Figure 5 : Battery Connector on Optional Power Supply
11.7 Alarm Wiring
Supervised alarm wiring is connected to a terminal block on the left side of the STAR-ELT
board. Termination requirements are described below.
11.8 Trouble Out Relay
A normally-closed relay is held open whenever the STAR-ELT is operating normally. This relay
closes when a local trouble condition is detected, such as a ground fault, power fault, or zone
wiring fault.
11.9 Zone Inputs
The STAR-ELT provides supervised contact closure inputs for up to four zone connections.
Supervision is based on a 10kΩ EOL resistor, which must be installed across the contacts in the
field. If an input is unused, an EOL resistor must be installed across those input terminals on the
STAR-ELT. Wiring integrity troubles are transmitted when they occur. Zone inputs are
normally-open, and activate when a contact closure is sensed. The type of event associated with
the zone (Alarm, trouble, supervisory, security, waterflow, tamper, etc) is programmed at the
receiver for each zone.
IMPORTANT: Only one dry contact must be connected to a zone input
11.10 FACP Power And Battery Trouble Inputs
The STAR-ELT provides inputs for monitoring FACP battery trouble (TB3-3, TB3-4) and FACP
AC power fail (TB3-5, TB3-6) conditions. These are generally used when the STAR-ELT is
powered by an FM approved FACP. These are dry contact inputs and are intended to be
connected to FACP dry relay contacts that provide the FACP power status. When used, the
wiring to these contacts must be in conduit and the STAR-ELT must be located in the same room
and within 20 ft of the FACP.
Battery
Connect
or (J1)