Installation Manual

Kingfisher Company, inc. STAR-ELT Manual
KCi #99420-MAN Rev 0.6 Page 15 of 29
Figure 7 Lower Left Corner of Main PCB - Zone Inputs
12.2 Ground Fault Indicator (LED9)
When a ground fault is detected on any input zone wiring, the zone indicator LED will illuminate
yellow to indicate a trouble condition on that zone, and the Ground Fault LED in the lower left
hand corner of the board will illuminate as well.
11.3 Test / Program (LED3)
This led is located next to the TEST / PROGRAM switch. This LED will illuminate GREEN
when the Test / Program switch is pressed momentarily, indicating that the unit is in
programming mode. This LED will illuminate YELLOW when the Test / Programming button
is depressed for 3 seconds to indicate that the unit is in TEST mode and sending a test
transmission.
11.4 Antenna Supervision (LED1)
Located next to the antenna BNC connector. This LED illuminates YELLOW to indicate an
antenna supervision fault condition.
TB1 Trouble
Relay
TB2 1-2 Zone 1
TB2 3-4 Zone 2
TB2 5-6 Zone 3
TB2 7-8 Zone 4
LED9 Ground
Fault LED
TB3 FACP 24VDC Input and
Power Status Monitoring