Installation Manual
Kingfisher Company, inc. STAR-ELT Manual
KCi #99420-MAN Rev 0.6 Page 26 of 29
STAR Transmitter
Parameter
Description
Factory
Maintenance
Field
# Fcn Digits
The number of digits used to
send alarm function codes
(must match the setting for the
entire system).
S
S
V
# Alarm Rounds
The number of times each
alarm message is transmitted.
This value, usually 3, may be
dictated by regulatory
standards.
S
S
# Test Rounds
The number of times each test
message is transmitted.
S
S
Time Between
Rounds (Round 1-2
and Round 2-3)
The number of seconds that
elapse between sending
multiple rounds of Alarm or
Test. These values are
automatically generated
randomly based on the
“Transmitter Address” but can
also be forced to any values
between 2 sec and 12 sec if
desired.
S
V
V
Next Test Time
The time, in 24-hour clock
format, that the next test will
be sent.
S
S
S
Current Time
The current local time, in 24-
hour clock format. See
“Synchronize with Computer
Time”
S
S
S
Synchronize with
Computer Time
When checked, the current
time written to the transmitter
is equal to the time set in the
computer. When checked, the
“Current Time” box is not
visible.
S
S
S
Time Between Tests
(Hours, Mins)
Set the time that elapses
between transmitting an
automatic test message.
Usually this is set to 24 hours,
0 min. It should never be set to
less than 0 hours, 2 min or
greater than 24 hours, 0 min
S
S
S