5. Specifications
Alarm Interface
Monitored Dry Contact Inputs
4 (each input monitors ONE dry contact)
Ground Fault Detection Resistance
< 100 Ω
Input Debounce Time
Programmable 1-99 sec
Input Termination Resistance
10 kΩ
Dry Contact Trouble Output
1 (Energized Contact, Normally Closed) 30VDC 1A
Resistive
Power Sources
DC Power Input
Source
24V Aux power from FM Approved FACP
Voltage Range
24V Nominal (20.4V to 26.5V)
Input Power Isolation
Optional Power Isolation Module
Power Source Fuse
2ASB (KCi #30040)
DC Current Draw – Standby
100mA average / 115mA peak
DC Current Draw – Transmission
300 mA average / 370mA peak
AC Power Input (Input)
Optional power supply AC Voltage
Range
120 / 240 VAC Nominal, Single Phase
Optional Power Supply AC Frequency
50-60 Hz
Optional Power Supply AC Current
Draw
< 0.5 A
Optional Power Supply AC Fuse
1A 3AG
Optional Backup Battery Type
Sealed Lead Acid
Optional Backup Battery Voltage
12.0 V nominal
Optional Backup Battery Standby
Duration
> 96 Hr (7.0 A-H or 5.0 A-Hr, such as KCi PN
17014)
Optional Backup Battery Recharge
Duration
< 24 Hr
Optional Battery Fuse
2ASB (KCi p/n 30040)
Optional Low Battery Indication
Threshold
12.6 V ± 0.1 V
Optional Battery Cutoff Threshold
11.3 V ± 0.1 V
Power Down Clock Time Retention
approximately 30 days
Indicators
AC Power Present
Green LED on optional Power Supply Module
Power Trouble
Flashing Yellow LED on Interface Module
Alarm Input
Red LED, adjacent to each input on Interface
Module