97-1501-12 Rev.
Output Interfaces for SVS2000TM Installation & Operation Manual CONTENTS I. INTRODUCTION . ..................................................................................................................................... 1 II. INSTALLING THE OUTPUT INTERFACE.................................................................................................. 1 III. SETTING UP THE OUTPUT OPTION CARD............................................................................................. 2 IV.
www.kistlermorse.com I. INTRODUCTION This manual covers the installation, setup and program commands for interfacing the SVS2000™ to a PLC on a DeviceNet, EtherNet/IP™ network or Profibus DP network.
www.kistlermorse.com III. Setting up the output Card for the SVS2000 A network consists of two or more nodes interconnected that each have a unique address. For each installation, unique parameters must be configured in the output module prior to connecting the module to the network so a conflict or error does not occur.
www.kistlermorse.com j. When the desired baud rate is displayed, press the ‘ENTER’ key. The display reads: BAUD RATE k. Press the ‘GROSS’ key to exit the PLC Menu Tree. If you started this procedure with the SVS2000 Field Firmware Upgrade then you will need to go back to those instructions now in order to restore the calibration/setup parameters. FOR ETHERNET/IPTM The Ethernet/IPTM Module is shipped from the factory configured for an IP address of 192.168.1.2 with a Subnet Mask of 255.255.255.
www.kistlermorse.com FOR PROFIBUS DP The Profibus Module is shipped from the factory configured for node 4. The node address is changeable via the DIP switches on the Profibus PCB Module. Switches one (1) through eight (8) configure the node address where switch one (1) is the LSB and switch eight (8) is the MSB. When the switch is in the on position the value is a one (1), and when the switch is off the value is zero (0). The Profibus Module will auto baud to the network baud during power-up.
www.kistlermorse.com V. SETTING UP THE PROFIBUS MODULE Once the signal processor is wired into the Profibus DP network with a valid node address and powered up, it should be possible for the device to be added to the configuration of the PLC. A copy of the GSD is included with the product and is located on the CD. The GSD can also be downloaded from the website, www.kistlermorse.com. See the screen shots below of a typical installation. 97-1501-12 Rev.
www.kistlermorse.com 6 97-1501-12 Rev.
www.kistlermorse.com VI. PLC INPUT/OUTPUT CONFIGURATION TABLE At this point weight data and status should be received by the PLC. The PLC should be able to set the required tare command bit in order to force the SVS2000 to tare and read/write a supported variable. Currently there are only two (2) supported variables that can be read/written. Read/write is optional and not required for gross/net values.
www.kistlermorse.com VII. troubleshooting Staus indicators are as follows: FOR DEVICENET LED Network Status (NS) Module Status (MS) Off Not on-line or no power to the system.
www.kistlermorse.com VIII. BOARD LAYOUT & WIRING SINGLE OPTION CARD INSTALLATION 4-20 mA Output Card OPTION CARD INSTALLATION or Serial Output Card 97-1501-12 Rev.
www.kistlermorse.com DEVICENET WIRING CONNECTION PLC or DEVICENET peripheralperipheral equipment. equipment. ToToPLC orother other DEVICENET Acceptable cable types are Belden 3084A or equivallent. Acceptable cable types are 3084A To To prevent ground loops, ground the Belden signal shield wire onlyor at equivalent. 0ne end. prevent ground loops, ground the signal shield wire only at one end. ETHERNET/IP WIRING CONNECTION Plug ethernet cable into ethernet connector/plug (RJ45) in the SVS2000 unit.
www.kistlermorse.com Notes 97-1501-12 Rev.
150 Venture Boulevard Spartanburg, SC 29306 Tel: (800) 426-9010 Tel: (864) 574-2763 [Local] Fax: (864) 574-8063 sales@kistlermorse.com www.kistlermorse.com 2013 All rights reserved. All data subject to change without notice. 97-1501-12 Rev.