User Manual
50
97-1129-01 Rev. D
www.kistlermorse.com
5. Press an Arrow Key to toggle the setpoint between On and Off.
A. Press the Enter Key to exit the test for this setpoint.
C. Repeat Steps 4 and 5.
7. Press the Gross or Net Key to terminate the test and return to Run Mode. Once the test is terminated,
the setpoints return to automatic control.
I-OUTPUT
MENU [40]
The I-Output Menu is used to enter parameters for current output, calibrate the current output to the receiving
each of the current output parameters and detailed navigation procedures through the menu tree. Current output
SVS2000.
41-46 CURRENT OUTPUT SETUP PARAMETERS
examples. The Setting Up Current Output section provides the procedure for using the SVS2000.
DESCRIPTIONS
41 IOut Range
The current transmitter can be set up to output 4-20 mA or 0-20 mA. This menu is
used to select one of the two operating ranges. The default is 4-20 mA.
Sets the low current (4 mA or 0 mA) operation point. The value entered determines
the weight where the transmitter outputs the minimum current. The ‘-’ Key toggles
between positive and negative for the value entered. The default value is 0.
Sets the high current (20 mA) operation point. The value entered determines the
weight where the transmitter outputs the maximum current. The ‘-’ Key toggles
between positive and negative for the value entered.
menu you can change the value.
2. The value entered for the 4/0 mA operation point can be smaller than or larger
than the value entered for the 20 mA operation point.