Dimension Guide

DIMENSION GUIDE
4 of 12
Electrical Requirements
If codes permit and a separate ground wire is used, it is
recommended that a qualied electrical installer determine that
the ground path and the wire gauge are in accordance with local
codes.
Check with a qualied electrical installer if you are not sure the
oven is properly grounded.
This oven must be connected to a grounded metal, permanent
wiring system.
Be sure that the electrical connection and wire size are
adequate and in conformance with the National Electrical Code,
ANSI/NFPA 70-latest edition or CSA Standards C22.1-94,
Canadian Electrical Code, Part 1 and C22.2 No. O-M91-latest
edition, and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
Electrical Connection
To properly install your oven, you must determine the type of
electrical connection you will be using and follow the
instructions provided for it here.
Oven must be connected to the proper electrical voltage and
frequency as specied on the model/serial/rating plate. The
model/serial/rating plate is located under the control panel
on single ovens and under the control panel on the upper
oven cavity on double ovens. See the following illustration.
Models rated from 7.3 to 9.6 kW at 240 V (5.4 to 7.4 kW at
208 V) require a separate 40 A circuit. Models rated at
4.8 kW and below at 240 V (3.6 kW and below at
208 V) require a separate 20 A circuit.
A circuit breaker is recommended.
Connect directly to the fused disconnect (or circuit breaker
box) through exible, armored or nonmetallic sheathed,
copper cable (with grounding wire). See the “Make Electrical
Connection” section in the Owner’s Manual.
Flexible conduit from the oven should be connected directly
the junction box.
Fuse both sides of the line.
Do not cut the conduit. The length of conduit provided is for
serviceability of the oven.
A UL listed or CSA-approved conduit connector must be
provided.
If the house has aluminum wiring, follow the procedure
below:
Connect the aluminum wiring using special connectors
and/or tools designed and UL listed for joining copper to
aluminum.
Follow the electrical connector manufacturer’s recommended
procedure. Aluminum/copper connection must conform with
local codes and industry-accepted wiring practices.
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
WARNING
A
A. Model/serial/rating plate