Installation Sheet

6
Electrical Requirements
If codes permit and a separate ground wire is used, it is
recommended that a qualied electrical installer determine
thatthe ground path and the wire gauge are in accordance
withlocal codes.
Check with a qualied electrical installer if you are not
suretheoven is properly grounded.
This oven must be connected to a grounded metal,
permanentwiring system.
Be sure that the electrical connection and wire size are
adequateand in conformance with the National Electrical
Code,ANSI/NFPA 70 — latest edition or CSA Standards C22.
1-94, Canadian Electrical Code, Part 1 and C22.2 No.
O-M91 — latest edition, and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
Electrical Connection
To properly install your oven, you must determine the type
ofelectrical connection you will be using and follow the
instructions provided for it here.
Oven must be connected to the proper electrical voltage and
frequency as specied on the model/serial/rating plate. The
model/serial/rating plate is located under the control panel
on single ovens and under the control panel on the upper
oven cavity on double ovens. See the following illustrations.
A
A
Single Oven
A. Model/serial/rating plate
Double Oven
A. Model/serial/rating plate
Models rated from 7.3 to 9.6 kW at 240 volts (5.4 to 7.4kW
at 208 volts) require a separate 40-amp circuit. Models
ratedat 4.8 kW and below at 240 volts (3.6 kW and below
at208 volts) require a separate 20-amp circuit.
A circuit breaker is recommended.
Connect directly to the circuit breaker box (or fused
disconnect) through exible, armored, or nonmetallic
sheathed, copper cable (with grounding wire). See the
“MakeElectrical Connection” section.
Flexible conduit from the oven should be connected
directlyto the junction box.
Fuse both sides of the line.
Do not cut the conduit. The length of conduit provided
isforserviceability of the oven.
A UL Listed or CSA Approved conduit connector
mustbeprovided.
If the house has aluminum wiring, follow the
procedurebelow:
Connect the aluminum wiring using special connectors
and/or tools designed and UL listed for joining copper to
aluminum.
Follow the electrical connector manufacturer’s recommended
procedure. Aluminum/copper connection must conform with
local codes and industry accepted wiring practices.
Voltage Single Double
240 VAC 5.8 kW 9.6 kW
208 VAC 4.4 kW 7.7 kW