Tone Tone Type Tone Description / Application Dip Switch 3rd Stage Peak Sound
(S1/S2) Tone Level (dBA@1m)
1
. 970Hz (BS5839-1:2002) O-O-O-O-O-O 18 118
2. 800Hz/970Hz @ 2Hz (BS5839-1:2002) O-O-O-O-O-I 1 120
3. 800Hz 970Hz @ 1Hz (BS5839-1:2002) O-O-O-O-I-O 1 120
4. 970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002) O-O-O-O-I-I 1 118
5. 970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002) O-O-O-I-O-O 1 118
6
. 554Hz, 0.1s/ 440Hz, 0.4s (France AFNOR NF S 32 001 ) O-O-O-I-O-I 1 119
7
. 500 1200Hz, 3.5s/ 0.5s OFF (Netherlands NEN 2575:2000) O-O-O-I-I-O 1 120
8
. 420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone) O - O - O - I - I - I 1 116
9
. 500 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia AS1670 Evacuation tone) O-O-I-O-O-O 1 119
1
0. 550Hz/440Hz @ 0.5Hz O-O-I-O-O-I 19 119
11. 970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone) O-O-I-O-I-O 1 118
12. 2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone) O - O - I - O - I - I 1 111
13. 1200Hz 500Hz @ 1Hz (DIN 33 404) O-O-I-I-O-O 1 119
14. 400Hz O - O - I - I - O - I 18 115
15. 550Hz, 0.7s/1000Hz, 0.33s O - O - I - I - I - O 1 120
1
6. 1500Hz 2700Hz @ 3Hz (Vandal Alarm) O - O - I - I - I - I 1 118
1
7. Simulated Bell O-I-O-O-O-O 1 114
18. 840Hz O-I-O-O-O-I 1 119
19. 660Hz O-I-O-O-I-O 10 114
20. 660Hz 1.8s ON/1.8s OFF O - I - O - O - I - I 19 114
21. 660Hz 0.15s ON/0.15s OFF O-I-O-I-O-O 19 113
22. 510Hz, 0.25s/ 610Hz, 0.25s O - I - O - I - O - I 1 115
23. 800/1000Hz 0.5s each (1Hz) O - I - O - I - I - O 1 119
2
4. 250Hz 1200Hz @ 12Hz O - I - O - I - I - I 1 115
2
5. 500Hz 1200Hz @ 0.33Hz. O-I-I-O-O-O 1 119
26. 2400Hz 2900Hz @ 9Hz O - I - I - O - O - I 1 113
2
7. 2400Hz 2900Hz @ 3Hz O - I - I - O - I - O 1 114
28. 800Hz 970Hz @ 100Hz O - I - I - O - I - I 1 119
29. 800Hz 970Hz @ 9Hz O - I - I - I - O - O 1 119
30. 800Hz 970Hz @ 3Hz O - I - I - I - O - I 1 120
31. 800Hz, 0.25s ON/1s OFF O - I - I - I - I - O 1 120
32. 500Hz 1200Hz, 3.75s/0.25s OFF (AS2220) O - I - I - I - I - I 1 120
33. 340Hz I-O-O-O-O-O 1 113
34. 1000Hz I-O-O-O-O-I 18 116
35. 1400Hz 1600Hz, 1s/1600Hz 1400Hz, 0.5s (NF 48-265) I-O-O-O-I-O 1 119
36. 660Hz 6.5s ON/13s OFF I - O - O - O - I - I 19 114
37. 1000Hz/2000Hz, 1s each I-O-O-I-O-O 1 116
38. 720Hz, 0.7s ON/0.3s OFF I - O - O - I - O - I 1 118
39. 970Hz, 0.25s ON/OFF I - O - O - I - I - O 1 118
40. 2800Hz, 1s ON/OFF I - O - O - I - I - I 1 111
41. 2800Hz 0.25s ON/OFF I-O-I-O-O-O 1 111
42. 2400/2900 @ 2Hz I - O - I - O - O - I 1 114
43. Chime, 554Hz/440Hz Single shot ‘ding dong’ I - O - I - O - I - O1 116
44. Chime, 554Hz/440Hz Repeating ‘ding dong’ I - O - I - O - I - I 1 116
45. Chime, 970Hz/800Hz Single shot ‘ding dong’ I- O - I - I - O - O 1 117
46. Chime, 970Hz/800Hz Repeating ‘ding dong’ I - O - I - I - O - I1 117
47. Hooter, Repeating I - O - I - I - I - O 1 115
48. Gentle alarm - Tone 2, rises slowly to full volume over 30s I - O - I - I - I - I 1 120
49. Time-Out Alarm As Tone 2, cuts off after 10 mins I-I-O-O-O-O 1 120
50. Time-Out Alarm As Tone 2, cuts off after 2 mins I - I - O - O - O - I 1 120
51. 750Hz 0.33s ON/0.51s OFF I - I - O - O - I - O 1 118
52. 750Hz 0.51s ON/0.33s OFF I - I - O - O - I - I 1 119
53. 550Hz, 0.33s/1000Hz, 0.7s I - I - O - I - O - O 1 116
54. 600Hz 900Hz/ 0.9s I - I - O - I - O - I 1 119
55. 660Hz 680Hz/ 0.9s I - I - O - I - I - O 1 116
56. 670Hz 725Hz/ 0.9s I - I - O - I - I - I 1 118
57. 920Hz 750Hz/ 0.9s I - I - I - O - O - O 1 119
58. 700Hz - 900Hz, 0.3s/0.6s OFF I - I - I - O - O - I 1 120
59. 900Hz - 760Hz, 0.6s/0.3s OFF I - I - I - O - I - O 1 119
60. 750Hz I - I - I - O - I - I 18 118
61. Power Only Use with Stage 3 control for manual/intermittent chime triggering I - I - I - I - O - O 43
62. Power Only Use with Stage 3 control for manual/intermittent chime triggering I - I - I - I - O - I 43
63. Power Only Use with Stage 3 control for manual/intermittent horn triggering I - I - I - I - I - O 47