8.4.1.10 Water-level alarm malfunction diagnosis and solution (For cassette / ducted)
Malfunction decision
conditions
If the sampling voltage is not 5V, the LED will display the
failure.
Supposed causes
Wiring mistake
Water-level switch faulty
Water pump faulty
Indoor PCB faulty
If the water-level switch
is inserted well?
If the water-level switch
is inserted well?
No
Insert the water-level switch well
Insert the water-level switch well
If the water-level switch
is broken?
If the water-level switch
is broken?
Yes
Replace the water-level switch
Replace the water-level switch
Replace the water pump, If
malfunction is still not
solved
Replace the water pump, If
malfunction is still not
solved
Yes
No
Yes
Replace the indoor main PCB
Replace the indoor main PCB
Power off, then restart the unit 3 minutes
later. Is it still displaying the error code?
Power off, then restart the unit 3 minutes
later. Is it still displaying the error code?
Yes