9.3.4 Fan speed has been out of control diagnosis and solution(E3)
Error Code
E3/F5
Malfunction decision
conditions
When indoor fan speed keeps too low (300RPM) for certain time, the
unit will stop and the LED will display the failure.
Supposed causes
Wiring mistake
Fan assembly faulty
Fan motor faulty
PCB faulty
Trouble shooting:
Power off, then restart the
unit 2 minutes later
Shut off the power supply,
Rotate the fan by hand.
The unit operates normally.
Find out the cause and have
it solved
Check the wiring of fan
motor
No
Yes
No
Correct the connections.
No
NoReplace the fan motor
Yes
Yes
Measure the voltage for the
fan motor from the main
PCB refer to the
Appendix 1
Yes
Replace the main PCBNo