For 24K:
At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of
them is 0 or close to 0, the IPM is defective. Otherwise, please follow the procedure below:
Yes
Check whether the power voltage
is normal.
Check whether the power voltage
is normal.
Measure whether outdoor terminal
voltage is normal
Measure whether outdoor terminal
voltage is normal
Restart the unit when the power supply
gets normal
Restart the unit when the power supply
gets normal
No
Yes
No
Reconnect it well
Reconnect it well
Yes
Measure whether the voltage
between L and N is normal
Measure whether the voltage
between L and N is normal
Yes
Measure whether input voltage of
bridge rectifier is normal
Measure whether input voltage of
bridge rectifier is normal
No
No
Check the wiring of
power wires well or
correctly
Check the wiring of
power wires well or
correctly
Reconnect it well
Reconnect it well
Check the wiring of L
and N well or correctly
Check the wiring of L
and N well or correctly
Reconnect it well
Reconnect it well
Check the wiring of
bridge rectifier well or
correctly
Check the wiring of
bridge rectifier well or
correctly
No
Yes
Replace the PFC module(If has)
Replace the PFC module(If has)
No
Measure whether the voltage
between P and N is normal
refer to the Appendix 4
Measure whether the voltage
between P and N is normal
refer to the Appendix 4
Replace the bridge rectifier
Replace the bridge rectifierNo
Check whether bridge
rectifier is normal
Check whether bridge
rectifier is normal
Check the wiring of reactor
or inductance
Check the wiring of reactor
or inductance
Reconnect the wiring
Reconnect the wiring No
Check whether reactor or
inductance is normal
Check whether reactor or
inductance is normal
Yes
Replace reactor or
inductance
Replace reactor or
inductance
No
Check whether the connecting
wire between main board and the
IPM board is connected tightly
Check whether the connecting
wire between main board and the
IPM board is connected tightly
Reconnect it well
Reconnect it well
No
Check if the outdoor unit
ventilation is good
Check if the outdoor unit
ventilation is good
Yes
Make the outdoor unit ventilate well
Make the outdoor unit ventilate well
Check whether the refrigerant system is ok
Check whether the refrigerant system is ok
No
Check if the outdoor fan runs
properly
Check if the outdoor fan runs
properly
please refer to the solution of [fan speed
has been out of control malfunction] .
Find out the cause and have it solved.
please refer to the solution of [fan speed
has been out of control malfunction] .
Find out the cause and have it solved.
No
Yes
No
Yes
Yes
Check the compress is
normal
Check the compress is
normal
Yes
Replace the compressor
Replace the compressorNo
Replace IPM board
Replace IPM board
Replace the outdoor main PCB
Replace the outdoor main PCB
No
Check whether the connecting
wire of the compressor is
connected correctly or tightly
Check whether the connecting
wire of the compressor is
connected correctly or tightly
Reconnect it well
Reconnect it well
No
Yes
Yes