INSTALLATION KUIR - KFUF Series MANUAL Ceiling And Floor Type Thank you very much for purchasing our air conditioner, Before using your air conditioner , please read this manual carefully and keep it for future reference.
Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock and fire. CONTENTS PAGE PRECAUTIONS.......................................................................................1 INSTALLATION INFORMATION................................................................2 ATTACHED FITTINGS..............................................................................3 INSPECTING AND HANDLING THE UNIT.............................
If the refrigerant leaks during installation, ventilate the area immediately. Toxic gas may be produced if the refrigerant comes into the place contacting with fire. The appliance shall be installed in accordance with national wiring regulations. Do not operate your air conditioner in a wet room such as a bathroom or laundry room. The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
3. ATTACHED FITTINGS Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully. NAME Remote controller & Its Holder Others SHAPE QUANTITY 1. Remote controller (on some models) 1 2. Remote controller holder (on some models) 1 3. Mounting screw(ST2.9×10-C-H) 2 4. Alkaline dry batteries (AM4) 2 5. Owner's manual 1 6. Installation manual 1 7.
4. INSPECTING AND HANDLING THE UNIT 5.2 Install the main body At delivery, the package should be checked and any damage should be reported immediately to the the service agent. When handling the unit, take into account the following: B Fragile, handle the unit with care. 1 Keep the unit upright in order to avoid compressor damage. D. Connecting point of refrigerant pipe (D. gas side) Choose on before hand the path along which the unit is to be brought in.
2. Ceiling Installation 20mm NEW CONCRETE BRICKS Inlaying or embedding the screw bolts. (Blade shape insertion) (Slide insertion) Fig.5-4 Steel bar Fig. 5-10 Embedding screw bolt (Pipe hanging and embedding screw bolt) Fig.5-5 D. Connecting point of refrigerant pipe (D.gas side) FOR ORIGINAL CONCRETE BRICKS E. Connecting point of refrigerant pipe (E. Liquid side) Install the hanging hook with expansible bolt into the concrete deep to 45~50mm to prevent loose. Fig.
6. OUTDOOR UNIT IN ALLATION Outdoor Unit Installation Instructions The area must be f ree of combustible gases and chemicals. Step 1: Select installation location. The pipe length between the outdoor and indoor unit may not exceed the maximum allowable pipe length. The outdoor unit should be installed in the location that meets the following requirements: If possible, DO NOT install the unit whe re it is exposed to direct sunlight.
Split Type Outdoor Unit (Refer to Fig 6.4, 6.5, 6.6, 6.10 and Vertical Discharge Table 6.1) Type Outdoor Unit (Refer to Fig 6.7, 6.8, 6.9 and Table 6.2) (W all or obstacle) Air Outlet H >120cm / 47 Fig. 6.4 W W Fig. 6.7 H W H Fig. 6.5 D Fig. 6.8 A D (W all or obstacle) B Fig. 6.6 >30cm / 11.8”Air inlet Table 6.1: Length Specifications of Split Unit (unit: mm/inch) Outdoor Unit Dimensions WxHxD Type Outdoor Mounting Dimensions Distance A >30cm / 11.8 >30cm / 11.
NOTE: The minimum distance between the outdoor unit and walls described in the installation guide does not apply to airtight rooms. Be su e to keep the unit unobstructed in at least two of the three directions (M, N, P) (See Fig. 6.10) / 11.8 ”o n l e M 30 cm / 11 m fro .8” w ck ba 2. Using a 65-mm (2.5”) co re drill, drill a hole in the wall. NOTE: When drilling the wall hole, make su re to avoid wi res, plumbing, and other sensitive components. ft / 23.
8. IN ALL THE CONNECTING PIPE Safety P recautions Table 8.1: The Maximum Length And Drop Height Based on Models. (Unit: m/ft.) Type of model Capacity (Btu/h) 12K 15/49 8/26 All field piping must be completed by a licensed technician and must comply with the local and national regulations. 50Hz T1 Condition/R22 Split Type 18K-24K 30/98.4 10/32.8 30K-42K 50/164 20/65.
Refrigerant Piping Connection Instructions CAUTION • The branching pipe must be installed horizontall y. An angle of mo re than 10° may cause malfunction. DO NOT install the connecting pipe until both indoor and outdoor units have been installed. Insulate both the gas and liquid piping to p revent water leakage. • • Step 2: Remove burrs. Burrs can a ffect the ai r-tight seal of refrigerant piping connection. They must be completely removed. 1.
6. Place flaring tool onto the form. 7. Turn the handle of the flaring tool clockwise until the pipe is fully fla red. Flare the pipe in acco rdance with the dimensions shown in table 8-2. Table 8.2: PIPING EXTENSION BEYOND FLARE FORM Pipe gauge Tightening to rque Fla re dimension (A) (Unit: mm/Inch) Min. Max . Ø 6.4 14.2-17.2 N.m (144-176 kgf.cm) 8.3/0.3 8.3/0.3 Ø 9.5 32.7-39.9 N.m (333-407 kgf.cm) 12.4/0.48 12.4/0.48 Ø 12.7 49.5-60.3 N.m (504-616 kgf.cm) 15.4/0.6 15.8/0.6 Ø 15.9 61.
9. AIR EVAC TION Flare nut Safety P recautions CAUTION • Cap Use a vacuum pump with a gauge reading lower than -0.1MPa and an air discharge capacity above 40L/min. • The outdoor unit does not need vacuuming. DO NOT open the outdoor unit ’s gas and liquid stop valves. • Ensure that the Compound Meter reads -0.1MPa or below after 2 hours. If after th ree hours of operation and the gauge reading is still above -0.1MPa, check if the re is a gas leak or water inside the pipe.
10. WIR Connect the connective cables to the terminals as identified with their respective mached numbers on the terminal block of indoor and outdoor units. The appliance shall be installed in accordance with national wiring regulations. Re-install the cover or the protection board. The air conditioner should use separate power supply with rated voltage. 10.
The Specification of Power(indoor power supply) Table 10-1 18 24 PHASE 1Phase FREQUENCY AND VOLT MODEL POWER CIRCUIT BREAKER/FUSE(A) 30~36 42~48 60 1Phase 1Phase 1Phase 1Phase 208-240 V 208-2 40V 208-2 40V 208-2 40V 208-2 40V 20 /16 40/25 50/30 60/45 60/50 Table 10-2 MODEL POWER 30~36 42~60 30~36 42~60 PHASE 3Phase 3Phase 3Phase 3Phase FREQUENCY AND VOLT 380-420 V 380-420 V 208-2 40V 208-2 40V 25/20 25/20 40/25 45/35 CIRCUIT BREAKER/FUSE(A) The Specification of
The Specification of Power(independence power supply) Table 10-5 18 24 30~36 42~48 60 PHASE POWER (indoor) FREQUENCY AND VOLT 1Phase 1Phase 1Phase 1Phase 1Phase 208-240 V 208-2 40V 208-2 40V 208-2 40V 208-2 40V CIRCUIT BREAKER/FUSE(A) 20/16 20/16 20/16 20/16 20/16 PHASE POWER (outdoor) FREQUENCY AND VOLT 1Phase 1Phase 1Phase 1Phase 1Phase 208-240 V 208-2 40V 208-2 40V 208-2 40V 208-2 40V CIRCUIT BREAKER/FUSE(A) 20/16 40/25 50/30 60/45 60/50 MODEL Table 10-6 MODEL 3
CAUTION The power supply is included in the power supply above mentioned can be applied to the table. Before obtaining access to terminals, all supply circuits must be disconnected. Wiring figure Fig.
Fig.10-5 Power supply Power supply Switch/Fuse (Available locally) Power wiring (indoor) Power linking wiring (Outdoor) Indoor Unit Out door Unit Ground wiring Weak elec-signal link wiring Ground wiring Ground the air conditioner properly in case to affect its anti-interference function Fig.
The Klimaire logo is a registered Trademark of Klimaire Products inc. Copyright 2016 Klimaire Products Inc. 2190 NW 89 Place, Doral, FL 33172 - USA Tel: (305)593-8358 Fax (305) 675-2212 www.klimaire.com sales@klimaire.com The design and specifications are subject to change without prior notice for product improvement.Consult with the sales agency or manufacturer for details.