Product Overview

Specifications and design subject to change without notice.
Single and Dual Duct
VAV Controllers
Specifications
Inputs and outputs
All inputs and outputs for SimplyVAV controllers
are set up at the factory and do not require eld
programming.
Inputs
Sensors are automatically detected
Inputs accept industry-standard 10K ohm
thermistors sensors.
Input overvoltage protection up to 24 volts AC,
continuous.
12-bit analog-to-digital conversion
Triac outputs
Optically isolated triac output.
Maximum switching 24 volts AC at 1.0 ampere
for each output
Maximum for controller is 3.0 amperes.
Analog outputs
Short-circuit protected
Output voltage 0–10 volts DC
30 mA per output, 30 mA total for all analog
outputs
12–bit digital-to-analog conversion
Description
The SimplyVAV series of controllers are an easy and
unique approach to operating a wide variety of VAV
terminal units. The integrated actuators, internal
airow sensors, and wide variety of application
programs make these BACnet Application
Specic controllers ideal for either new or retrot
installations.
Easy to install Just mount the controller, wire it
to a 24 volt transformer, and then connect airow
and temperature sensors. A SimplyVAV controller
automatically detects sensors as they are connected
without special programming or soware tools.
Simple, menu driven setup The controllers feature
simple, menu driven setup choices. No special
programming skills or soware tools are required
to choose applications, enter setpoints, set network
addressing, and balance airow. All options can
be set by using only an STE-8001 sensor which
can be installed as the permanent room sensor or
temporarily connected as a technician’s service tool.
New or retrot applications The SimplyVAV
controllers are ideal for new installations or
upgrades of older, less ecient controllers.
Staged, modulated, oating, or time proportional
reheat
Series or parallel fan control
Single or dual duct application
Native BACnet All models are BACnet Application
Specic Controllers that are ready to connect to a
BACnet MS/TP network. Device instance, MAC
address, and baud rate are set from an STE-8001
without special soware.
Easy system integration For SimplyVAV
installations that are part of a BACnet building
automation system, the controllers provide system
diagnostic indicators. Through the MS/TP network,
the controllers signal demands for higher static duct
pressure, cooler or warmer supply air, and when to
start air handler units.