Product Overview

Models
The table below illustrates the appropriate model for each application. If replacing a CSC-2001-22 or
CSC-2002-22 (now obsolete), use the CSC-2001, CSC-2002, CSC-2003, or CSC-2004 and mount appropriately.
Description
The pneumatic CSC-2000 series are designed for use
on VAV terminal units in HVAC systems. These are
dierential-pressure, sub-master controllers with
adjustable minimum and maximum airow seings.
A master controller, typically a room thermostat,
resets the CSC-2000 velocity setpoint.
Direct acting models are for normally open VAV
terminal units. Reverse acting are for normal closed
VAV terminal units.
Each is equipped with separate adjustment knobs
for minimum and maximum airow seings. All
models should be calibrated with the use of airow
measuring equipment.
Specifications and design subject to change without notice.
With 0–10 Molded Plastic Dial
(Mount with Face Up Only)
With Paper Label Dial
Direct Acting (Beige Controllers) for Normally Open Dampers
Model
Thermostat Required Setpoint Range
Reset Pressure
Band
Air Consumption Dial Face
For
Cooling
For
Heating
Minimum Maximum
CSC-2001
Direct
Acting
Reverse
Acting
0 to 1.0" wc
(249 Pa)
Min. plus 1.0"
wc (249 Pa)
8 ±0.5 to 13 psi
(55 ±3.5 to 90 kPa)
14.4 scim @ 20 psi
(3.93 mL/s @ 138 kPa)
0–10 Molded
Plastic
CSC-2003
14.4 scim @ 20 psi
(3.93 mL/s @ 138 kPa)
Paper Label
CSC-2007
11.5 scim @ 20 psi
(3.1 mL/s @ 138 kPa)
CSC-2009
0 to 2.0" wc
(498 Pa)
Min. plus 2.0"
wc (498 Pa)
14.4 scim @ 20 psi
(3.93 mL/s @ 138 kPa)
CSC-2017
11.5 scim @ 20 psi
(3.1 mL/s @ 138 kPa)
Reverse Acting (Gray Controllers) for Normally Closed Dampers
Model
Thermostat Required Setpoint Range
Reset Pressure
Band
Air Consumption Dial Face
For
Cooling
For
Heating
Minimum Maximum
CSC-2002
Reverse
Acting
Direct
Acting
0 to Max
0 to 1.0" wc
(249 Pa)
3 ±0.5 to 8 psi
(21 ±3.5 to 55 kPa)
14.4 scim @ 20 psi
(3.93 mL/s @ 138 kPa)
0–10 Molded
Plastic
CSC-2004
14.4 scim @ 20 psi
(3.93 mL/s @ 138 kPa)
Paper Label
CSC-2008
11.5 scim @ 20 psi
(3.1 mL/s @ 138 kPa)
CSC-2010
0 to Max
0 to 2.0" wc
(498 Pa)
14.4 scim @ 20 psi
(3.93 mL/s @ 138 kPa)
CSC-2018
11.5 scim @ 20 psi
(3.1 mL/s @ 138 kPa)
CSC-2000 Series
Reset Volume Controllers

Summary of content (2 pages)