Install Instructions

CSC-2000 Series Reset Volume Controllers 1 Installation Guide
Installation Guide
Reset Volume Controllers
CSC-2000 Series
Connections Adjustments
Any sequencing with other controllers, valves, or
pneumatic-electric relays must be sequenced with
the controllers reset range, not the actuators spring
range.
These controllers are typically used on single-duct
applications but may be found in dual-duct appli-
cations. When working on dual-duct applications
it may be necessary to work on one duct at a time
while closing o the other.
The CSC-2000 series controllers are position sensi-
tive. See the Mounting section on the next page for
the proper vertical/horizontal orientation for the dif-
ferent models.
CAUTION
Pneumatic devices must be supplied with clean,
dry control air. Any other medium (e.g., oil or
moisture contamination) will cause the device
to fail.
CSC-2000 Series Overview
The CSC-2000s are dierential-pressure (P), sub-
master controllers with adjustable minimum and
maximum airow seings. A master controller,
typically a room thermostat, resets the CSC velocity
setpoint.
CSC-2000s are available as direct acting for normally
open VAV terminal units, and reverse acting for nor-
mal closed VAV terminal units. Each unit is equipped
with separate adjustment knobs for minimum and
maximum airow seings. CSC-2001/2002s are
equipped with 0–10 reference dials, while all others
have blind adjustments. Calibrate all models using
standard airow measuring equipment.
The spring range of the actuator does not maer
to the controller. However, sucient main air is
required to provide the actuator with enough force
to operate the damper/linkage.