Product Overview

Features
Adjustabledirectorreverseactingreset(normal-
lyopenornormallycloseddamperseings)
Adjustableminimumandmaximumsetpoints
Availablein0to1"and0to2"wcdierential
pressureranges
Availablewithfactory-set3,8,or10psiresetstart
points(eld-adjustable0–10psiifnecessary)
SeeSpecications on page 2formoredetails
Accessories/Repair Parts
HFO-0006 In-linecontrol-airlter
HFO-0014 Gportrubbercapreplacement
HMO-4508 Mountingbracket
ICI-1005 Pressuregauge
SSS-1002 Flowsensor,onesensingpoint,
3-5/32"(80mm)length
SSS-1003 Flowsensor,twosensingpoints,
5-13/32"(137mm)length
SSS-1004 Flowsensor,threesensing
points,7-21/32"(195mm)length
SSS-1005 Flowsensor,foursensingpoints,
9-29/32"(252mm)length
Specifications and design subject to change without notice.
Description and Application 1
Models 1
Features 1
Accessories/Repair Parts 1
Details 2
Specifications 2
*(These specications do not apply to the CSC-3014/3501/3505.)
Description and Application
TheseCSC-3000seriesresetvolumecontrollersare
designedforuseonheatingorcoolingsystemswith
(normallyopenornormallyclosed)VAVterminal
unitsand(directorreverseacting)thermostats.
Theyaresub-masterairvelocitycontrollers.Each
isequippedwithseparateadjustmentknobsfor
minimumandmaximumairowsetpoints.Models
areavailablewithvariousresetstartpoints.Amaster
controller,typicallyaroomthermostat,resetsthe
CSC-3000betweentheminimumandmaximum
velocitysetpoints.
TheuniversaldesignoftheCSC-3000seriesis
intendedforneworreplacementapplicationsthat
callfordirectorreverseactingresetonnormally
openornormallyclosedVAVterminalunits.
Models
NOTE: SeealsoModel Selection Chart on page 2.
CSC-3011-10 0to1"range,8psistart
CSC-3016-10 0to2"range,8psistart
CSC-3017-16 (IdenticaltotheCSC-3011-10but
doesnotcomewithamounting
bracketorKMClogo.)
CSC-3021-10 0to1"range,3psistart
CSC-3023-10 0to1"range,10psistart
CSC-3025-10 0to2"range,8psistart(high
ow,forTrane
®
units)
CSC-3026-10 0to2"range,3psistart
NOTE: CSC-3000seriescontrollersareposition
sensitive.Theymustbemountedand
calibratedineitherthehorizontalor
verticalplane.
ForthediscontinuedCSC-3014andCSC-
3501/3505models,see their separate data
sheets.Forreplacementinformation,see
theCSCControllerCross-Reference.
CSC-3000 Series*
Reset Volume Controllers

Summary of content (2 pages)