Product Overview

Description
KMC REE-4001 relay modules are designed
primarily for use with VAV terminal units in
HVAC systems. When used with CTE series room
thermostats, up to three stag es of reheat may be
controlled. They may also be controlled by a 0 to 10
VDC output from a DDC or analog controller.
Each triac output circuit is capable of handling
contactors of up to 10 VA @ 24 VAC. The three
circuits are calibrated to actuate at equally spaced
intervals across the thermostat’s proportional band.
By using the REE-4001, the heating requirements of
a particular VAV terminal may be actuated in three
separate steps aording more precise temperature
control.
For controlling direct expansion compressors in
roof top units and other equivalent equipment, see
also the REE-4019 three-stage, wide-deadband relay
module.
Application
KMC REE-4001 Relay Modules are primarily intend-
ed for use with the following thermostat models:
CEE-1103
CTE-1004
CTE-1103
CTE-5002/5012
CTE-5202
Features
Controls up to three stages of reheat
Control is activated at equally spaced intervals
across a thermostat’s proportional band
Simple installation
Specifications and design subject to change without notice.
Specifications
Supply Voltage 24 VAC, +20%/–15% @ 1 VA
plus output loads
Input Signal 0 to 6 VDC
Switching Dierential 0.33 VDC (each stage)
Output Capacity 10 VA per stage @ 24 VAC
Connections Plated screw terminals
Wire Size 14 to 22 AWG, stranded
Material Beige ame-resistant plastic
Weight
2 oz. (57 grams)
Approvals SASO PCP Registration KSA
R-103263
Temperature Limits
Operating 40 to 120° F (4 to 49° C)
Shipping –40 to 140° F (–40 to 60° C)