Installation Guide
TP-6879 3/15 13Section 1 Installation
1.4.2 Exhaust Requirements
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
WARNING
Servicing the exhaust system. Hot parts can cause
severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely
hot during operation.
Figure 1-2 gives the exhaust temperature at rated load.
Mount the generator set so that the hot exhaust does not
blow on plants or other combustible materials. Maintain
the clearances shown in the dimension drawing in
Section 3.
Exhaust Model
Temperature,
_C(_F)
Exhaust gas exiting the
enclosure at rated kW,
_C(_F)
8RESV(L) 190 (374)
10/12RESV(L) 106 (224)
Figure 1-2 Exhaust Flow and Temperature
The generator set r equires correct air flow for cooling
and combustion. The inlet and outlet openings in the
sound enclosure provide the cooling and combustion
air. Figure 1-3 shows the locations of the cooling air
intake and exhaust vents. Inspect the air inlet and outlet
openings inside and outside the housing to ensure that
the air flow is not blocked.
tp6879
1. Air intake
2. Exhaust outlet
1
2
FRONT VIEW
Figure 1-3 Cooling Air Intake and Exhaust
1.5 Dimension Drawings
See the dimension drawings in Section 3 for the
generator set dimensions, fuel and electric inlet
locations, and recommended clearance.
1.6 Access the Air Intake Area
The battery, fuel system, and electrical connections are
located in the air intake area. Raise the roof and remove
the enclosure panel to access the air intake area during
installation as described below.
1. Remove panel screws and remove the panel. Pull
the panel up and off. See Figure 1-4.
2. To make the electrical connections, you will also
need to remove the cover panel over the terminal
block.
3. Reinstall the panels after all electrical connections
are complete and the battery is installed and
connected.
GM801 10
1. Panel screws
2. Left side panel
3. Electrical cover panel
1
1
2
3
Figure 1-4 Remove Left Panel