Installation Guide

TP-6879 3/15 25Section 1 Installation
RXT
4
PIM
LCM or a Load Shed Kit
Generator Set
COM
PWR
COM
PWR
B
A
B
A
COM
PWR
B
A
COM
PWR
B
A
1. Generator set terminal block. See Figure 3-4 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each c able shield to GROUND at the generator set.
3. Communication cable Belden #8762 or equivalent 20 AWG shielded, twisted-pair cable (one pair).
4. Connect shields together as shown.
5. Leave one end of each cable shield disconnected at the last device.
6. 12 AWG or 14 AWG leads for PWR and COM.
GND
1
2
5
6
Note: See Section 1.10.2, Cable Specifications.
COM
PWR
B
A
COM
PWR
B
A
A
B
COM
PWR
3
4
RBUS
12 VDC
TB3
3
Figure 1-23 Accessory Module Communication Connection Details