Product Specifications

G4-241 (10/12RESV) 3/15d
Fuel Requirements
Fuel System 10RESV 12RESV
Fuel types Natural Gas or LPG
Fuel supply inlet 1/2 NPT
Fuel supply pressure, kPa (in. H
2
O):
Natural gas .87--2.7 (3.5-11)
LP 1.7--2.7 (7-11)
Fuel Composition Limits *
Nat. Gas LPG
Methane, % by volume (minimum) 90 min.
Ethane, % by volume (maximum) 4.0 max.
Propane, % by volume 1.0 max. 85 min.
Propene, % by volume (maximum) 0.1 max. 5.0 max.
C
4
and higher, % by volume 0.3 max. 2.5 max.
Sulfur, ppm mass (maximum) 25 max.
Lower heating value,
MJ/m
3
(Btu/ft
3
), (minimum)
33.2 (890) 84.2 (2260)
* Contact your local distributor for suitability and rating derates based
on fuel compositions outside these limits.
Operation Requirements
Fuel Consumption
Model
Fuel
Type
% Load Fuel Consumption, m
3
/hr. (cfh)
10RESV
Natural
Gas
100
5.1 (179)
75
4.1 (145)
50
3.4 (120)
25
2.7 (97)
Exercise
2.1 (75)
LPG
100
2.5 (89)
75
2.0 (69)
50
1.5 (52)
25
1.1 (39)
Exercise
0.8 (29)
12RESV
Natural
Gas
100
6.1 (216)
75
4.5 (160)
50
3.6 (128)
25
2.8 (99)
Exercise
2.1 (74)
LPG
100
2.9 (103)
75
2.2 (76)
50
1.6 (57)
25
1.2 (42)
Exercise
0.8 (30)
Nominal fuel rating: Natural gas: 37 MJ/m
3
(1000 Btu/ft.
3
)
LPG: 93 MJ/m
3
(2500 Btu/ft.
3
)
LPG conversion factors: 8.58 ft.
3
=1lb.
0.535 m
3
=1kg
36.39 ft.
3
= 1 gal.
Sound Data
Model 10RESV and 12RESV 8 point logarithmic average sound
levels are 67 dB(A) during weekly engine exercise and 71 dB(A)
during full-speed generator diagnostics and normal operation.
The lowest point sound levels are 64 dB(A) and 69 dB(A)
respectively as compared to competitor ratings.*
All sound levels are measured at 7 meters with no load.
* Lowest of 8 points measured around the generator. Sound levels at other points
around generator may vary depending on installation parameters.
RDC2 Controller
V oltage: 240 V
Freq: 60.0 Hz
The RDC2 controller provides integrated control for the
generator set, Kohlerr Model RXT transfer switch,
programmable interface module (PIM), and load control module
(LCM).
The RDC2 controller’s 2-line LCD screen displays status
messages and system settings that are clear and easy to read,
even in direct sunlight or low light.
RDC2 Controller F eatures
D Membrane keypad
d OFF, AUTO, and RUN pushbuttons
d Select and arrow buttons for access to system
configuration and adjustment menus
D LED indicators for OFF, AUTO, and RUN modes
D LED indicators for utility power and generator set source
availability and ATS position (Model RXT transfer switch
required)
D LCD display
d Two lines x 16 characters per line
d Backlit display with adjustable contrast for excellent
visibility in all lighting conditions
D Scrolling system status display
d Generator set status
d Voltage and frequency
d Engine temperature
d Oil pressure
d Battery voltage
d Engine runtime hours
D Date and time displays
D Smart engine cooldown senses engine temperature
D Digital isochronous governor to maintain steady-state speed
at all loads
D Digital voltage regulation: ±1.0% RMS no-load to full-load
D Automatic start with programmed cranking cycle
D Programmable exerciser can be set to start automatically on
any future day and time, and run every week or every two
weeks
D Exercise modes
d Unloaded weekly exercise with complete system
diagnostics
d Unloaded full-speed exercise
d Loaded full-speed exercise (Model RXT ATS required)
D Front-access mini USB connector for SiteTecht or
USB Utility connection
D Integral Ethernet connector for Kohlerr OnCuer Plus
D Built-in 2.5 amp battery charger
D Remote two-wire start/stop capability for optional connection
of Model RDT or RSB transfer switches
See additional controller features on the next page.