Installation Guide

TP-6967 8/1516 Section 1 Installation
5. Remove the hose clamp and fuel hose from the
hose fitting. See Figure 1-10.
6. Use a straight-blade screwdriver to remove the NG
orifice from the hose fitting. See Figure 1-11.
7. Insert the LPG orifice into the hose fitting. Use a
straight-blade screwdriver to tighten the fitting until
it is snug.
8. Slide the hose onto the hose fitting and secure it
with the clamp.
9. Disconnect ignition timing leads 65 and N5 for
LPG. The ignition timing leads are located near the
fuel solenoid valve. See Figure 1-10.
Note: Do not disconnect the leads to the fuel
solenoid valve.
3
1. LPG fitting tied to regulator for shipping
2. Fuel hose and clamp
3. Ignition timing lead location (leads not shown)
2
Ignition Timing Lead Connection
1
Figure 1-10 Fuel System, As Shipped
10. Connect and turn on the new fuel supply.
11. Reconnect the generator set engine starting
battery leads, negative (--) lead last.
12. Reconnect the utility power to the generator.
13. Start the generator set by moving the master switch
to the RUN position.
14. Check for leaks using a gas leak detector.
15. Run the generator set and check the operation.
16. Move the generator set master switch to the
OFF/RESET position to shut down the generator
set.
Conversion from LPG to Natural Gas
To convert from LPG to natural gas, repeat the steps
above, removing the LPG fuel orifice and installing the
NG fitting. Connect ignition timing leads 65 and N5
together for natural gas.
1. Fuel orifice fitting
2. Hose fitting
3. Orifice tied to regulator for shipping
1
GM29253
2
3
Figure 1-11 Fuel Orifice Fitting Installation