TP-6515 1/1118 Section 2 Operation
Emergency Stopping (TRES Models Only)
Push the red emergency stop switch for immediate
generator set shutdown in the case of an emergency.
See Figure 2-4 for the emergency stop switch location.
The emergency stop switch shuts down the generator
set immediately. The c ontroller display shows AF
(auxiliary fault) when the emergency stop button is
activated.
Use the generator set master switch for normal
shutdowns.
1
GM66010
1. Emergency stop switch
Figure 2-4 Emergency Stop Switch, TRES Models
2.5.3 Resetting Emergency Stop Swi tch
(TRES Models only)
Use the following procedure to reset the generator set
after shutdown by the emergency stop switch. See
Section 2.6.3 to reset the generator set after a fault
shutdown.
1. Place the generator set master switch in the
OFF/RESET position.
2. Investigate and correct the cause of the
emergency stop.
3. Rotate the emergency stop switch knob clockwise
and release it. Check that the knob returns to the
deactivated (out) position.
4. Move the generator set master switch to the RUN
or AUTO position to restart the generator set.
Verify that the controller display no longer shows a
fault code. The generator set engine will not start
until the reset procedure is complete.