Operating Guide

Optional Temperature Limiting Adjustment
CAUTION: Risk of personal injury. The water temperature
should never be set above 120°F (49°C).
Turn the valve clockwise to the full open position and let the hot
water run for several minutes. Position a thermometer in the
water stream and check the temperature.
For minor water temperature changes, adjust the setscrew, and
recheck the water temperature.
For major water temperature changes, remove the O-ring and
collar from the valve stem. Slowly rotate the valve stem until the
desired water temperature is reached.
Reinstall the collar on the valve stem with the setscrew against
the side of the tab.
Reinstall the O-ring, rotate the valve stem counterclockwise to
shut the water off, and recheck the water temperature.
NOTE: After adjustment, complete the required information on the
valve label.
Setscrew
Tab
Valve Stem
Collar
Valve Label
O-Ring
Tab
Collar
Setscrew
HiFlow Valve
All Other Valves