3.2.2 LED Indicators
LEDs above the RUN, OFF, and AUTO buttons indicate the mode of operation as shown in Figure 32.
Power System LEDs indicate the status of the utility power and the generator set, and indicate which source is supplying power
to the building (based on the position of the RXT transfer switch). See Figure 32.
Note:
The power system LEDs operate only if a Model RXT transfer switch is connected.
LED
LED Operation
RUN
Lights when the generator set has been started locally by pressing the RUN button. Remote start and
stop commands are ignored.
OFF
Lights for 2 seconds, then flashes every 2 seconds when the generator set and controller are off.
Remote start/stop commands have no effect. The exercise cycle will not run.
In Auto mode, OFF LED flashes quickly to indicate a fault shutdown. Attention required. Identify and
correct the fault condition before resetting the controller.
AUTO
Lights when the generator is in automatic (standby) mode. Generator set will respond to engine start and
stop commands from the controller (for example, exercise start and stop commands) or an ATS. Time
delays operate as described in the Generator Set Operation section.
Utility Power Available *
Lights when utility power is available.
Building on Utility Power *
Lights when the building load is connected to utility power through the RXT transfer switch.
Generator Power Available *
Lights when generator power is available.
Building on Generator Power *
Lights when the building load is connected to generator power through the RXT transfer switch.
These LEDs operate only if a Model RXT transfer switch is connected.
Figure 32 RDC2 Controller LED Operation
3.2.3 LCD Display
The controller is equipped with a two-line x 16-character backlit digital display with adjustable contrast. When the generator is
running, the controller automatically scrolls through the displays shown in Figure 33. When the system is in standby mode and
the controller is in AUTO, the screens shown in Figure 33 are displayed.
When a fault or warning condition exists, the controller will show the corresponding message. See the Fault section for more
information about faults.
Controller menus display power system information, including status information for the engine, generator, and optional RBUS
accessories, exercise settings, and event history. Some menus allow changes to the controller settings. See the related sections
in the manual for menu diagrams.
The display contrast is adjustable. Navigate to the Genset System menu and step down to the Contrast screen. Press the Select
button, and then use the up and down arrow buttons to adjust the contrast. See the related sections in the manual, Changing
Settings, and Genset System Menu.
The display backlight turns off after about a minute of no activity. The backlight turns on when a button is pressed or when the
generator set starts.