Full Product Manual

60 TP-7092 4/23
3.18.2 Networking Configuration Submenu (OnCue
®
Password)
The networking Configuration menu includes settings used for communication with the Kohler
®
OnCue
®
Plus Generator
Management System.
Password
Note:
Use the OnCue password shown on the controller display for OnCue or OnCue
®
Plus applications.
For the initial OnCue
®
Plus setup, you will be required to reset the OnCue
®
password on the RDC2 controller, and then enter it
into the OnCue
®
Plus application. To reset the password, follow the instructions in Figure 48.
Note:
The password is displayed for only 10 seconds. Be sure to write down the password and serial number.
A new password is generated each time the reset password procedure is performed. If the password is reset after the OnCue
®
Plus system has been set up, the connection will be lost. Disconnect the battery power to the controller, wait a minute, then
reconnect power.
DHCP Submenu
For most applications, the Dynamic Host Configuration Protocol (DHCP) is enabled and the IP settings cannot be changed from
the controller keypad. If DHCP is enabled, IP parameters are not displayed.
If DHCP is disabled (i.e., if a static IP address is required), then the IP parameters can be modified. For applications that require
a static IP address, press and hold the select button to enable editing, press the down arrow to disable DHCP, and then step to
the next parameters and enter the information. See Figure 48.
If an error occurs while setting a parameter, an error message is displayed and then the controller exits the edit mode. Previous
settings are preserved.