The generator sets include a resettable thermostat. See Figure 68 for the thermostat location in the air intake area, near the fuel
system. The thermostat detects excess heat inside the enclosure. If the thermostat trips, the generator will shut down and the
controller will display a fault (underspeed, underfrequency, or undervoltage). Check for blocked air inlets and exhaust outlets.
Then follow these steps to reset the thermostat.
Procedure to Reset the Thermostat
1. Disconnect the utility power to the generator by opening (turning OFF) the corresponding circuit breaker at the building’s
distribution panel.
2. Open the enclosure roof and secure it with the roof stay on the left side of the enclosure.
3. Remove the air intake panel. See Figure 68.
4. Press the button on the thermostat to reset it.
5. Replace the air intake panel.
6. Reconnect utility power to the generator set by closing the circuit breaker in the distribution panel.
7. Reset the fault on the controller. Refer to the Faults section for instructions, if necessary.
Figure 68 Thermostat
Thermostat location
Thermostat reset
button