Spec Sheet

G4-245 (14RESA) 1/19c
Generator Ratings
Standby Ratings
Line Circuit
Breaker
Natural Gas LPG
Alternator Voltage Phase Hz kW/kVA Amps kW/kVA Amps Amps Poles
2F5
120 * 1 60 12/12 100 13/13 108 125 1
110/220 1 60 12/12 54 14/14 63 100 2
120/240 * 1 60 12/12 50 14/14 58 70 2
115/230
1 50 10/10 43 11/11 47 70 2
220[
1 50 10/10 45 11/11 50 50 1
230 1 50 10/10 43 11/11 47 50 1
240[
1 50 10/10 41 11/11 45 50 1
2G5
120/208 * 3 60 12/15 41 13/16 45 50 3
120/240 * 3 60 12/15 36 13/16 39 50 3
220/380 3 60 12/15 22 13/16 24 32 4
277/480 * 3 60 12/15 18 13/16 20 25 3
220/380]
3 50 10/12 18 11/13 20 25 4
230/400 3 50 10/12 18 11/13 19 25 4
240/416]
3 50 10/12 17 11/13 19 25 4
* UL listed.
[ 50 Hz single-phase models are factory-connected as 230 volts. Field-adjustable to 220 or 240 volts by an authorized service technician.
] 50 Hz 3-phase models are factory-connected as 230/400 volts. Field-adjustable to 220/380 or 240/416 volts by an authorized service technician.
Note: The line circuit breaker is automatically selected based on the generator set model and voltage configuration.
RATINGS: Standby ratings apply to installations served by a reliable utility source. All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. The standby
rating is applicable to variable loads with an average load factor of 80% for the duration of the power outage. No overload capacity is specified at this rating. Ratings are in accordance with ISO- 3046/1,
BS5514, AS2789, and DIN 6271. GENERAL GUIDELINES FOR DERATING: ALTITUDE: Derate 4% per 305 m (1000 ft.) elevation above 153 m (500 ft.). TEMPERATURE: Derate 2% per 5.5_C
(10_F) temperature increase above 16_C(60_F). Availability is subject to change without notice. The generator set manufacturer reserves the right to change the design or specifications without notice
and without any obligation or liability whatsoever. Contact your l ocal Kohler Co. generator distributor for availability.