Generator Set Dimensions and Weights
Overall Size, L x W x H: 1216 x 665 x 733 mm
(48 x 26.2 x 29 in.)
Shipping Weight (with ATS):
14RESAL 213 kg (470 lb.)
20RESAL 263 kg (580 lb.)
NOTE: Dimensions are provided for reference only and should not be used for planning
installation. Contact your local distributor for more detailed information.
H
L
W
G4-210 (14/20RESAL) 2/12a
Standard Generator Set Features
D ATS: Model RXT automatic transfer switch
D Battery cables
D Braided stainless steel flexible fuel line
D CARB- and EPA-certified fuel system
D Corrosion-proof polymer sound enclosure
D Critical silencer
D DC2 generator set/ATS controller
D Field-connection terminal block
D Fuel solenoid valve and secondary regulator
D Line circuit breaker:
14RESAL: 70 amps
20RESAL: 100 amps
D Multi-fuel system, LP vapor/natural gas, field-convertible
D Oil drain extension with shutoff valve
D Premium 5-year limited warranty
D 18-month limited warranty for non-standby (off-grid)
applications (14RESAL only)
D Rodent-resistant construction
D Sound-deadening, flame-retardant foam per UL 94,
class HF-1
Available Accessories*
Communication Accessories
- OnCuer G enerator Management System
Controller Accessories
- Programmable Interface Module (PIM)
(provides 2 digital inputs and 6 relay outputs)
- Load Control M odule (LCM)
(provides 4 power relays and 2 HVAC relays)
Electrical System
- Battery
- Battery heater
Maintenance
- Maintenance kit (air and oil filters)
- General maintenance literature kit
- Overhaul literature kit
- Production literature kit
Starting Aids
- Carburetor heater, 120 VAC (recommended for
reliable starting at temperatures below 0_C[32_F])
- Fuel regulator heater pad (20RESAL; recommended for
reliable starting at temperatures below --18_C[0_F])
RXT Transfer Switch Accessories
- Status indicator
Miscellaneous Accessories
- __________________________________________
- __________________________________________
* Accessories are available through Kohler authorized distributors and
dealers.
Model RXT Transfer Switch
D UL listed
D 240 VAC/60 Hz
D Withstand rating 10,000 amps with specified breakers
D Models:
d 100 amp model with load center is supplied with the
14RESAL
d 200 amp standard model is supplied with the 20RESAL
D Corrosion-resistant NEMA 3R enclosures can be installed
indoors or outdoors
D Designed for use only with Kohlerr generator sets equipped
with the RDC2 or DC2 controller
D See Specification Sheet G11--121 for more information
KOHLER CO., Kohler, Wisconsin 53044 USA
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales and service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPower.com
Kohler Power Systems
Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65) 6264-6422, Fax (65) 6264-6455
200 Amp with optional
status indicator shown.