Spec Sheet

G4-224 (150ERESC) 7/18e
Application Data
Lubrication
Lubricating System
Type Full Pressure
Oil pan capacity, L (qt.) w
8.0 (8.5)
Oil pan capacity with filter, L (qt.) w
8.5 (9.0)
Oil filter: quantity, type w
1, Cartridge
w Kohler recommends the use of Kohler Genuine oil and filters.
Cooling
Radiator System
Ambient temperature, _C(_F)
45 (113)
Engine jacket water capacity, L (gal.) 13.4 (3.54)
Radiator system capacity, including
engine, L (gal.)
25.5 (5.6)
Engine jacket water flow, Lpm (gpm) 125 (33)
Heat rejected to cooling water at rated
kW, dry exhaust, kW (Btu/min.)
88.2 (5021)
Heat rejected to charge cooling air at
rated kW, dry exhaust, kW (Btu/min.)
11.3 (642)
Heat rejected to engine oil at rated kW,
dry exhaust, kW (Btu/min.)
1.4 (81)
Water pump type Centrifugal
Fan diameter, including blades, mm (in.) 711 (28.0)
Fan, kWm (HP) 18.7 (25)
Max. restriction of cooling air, intake and
discharge side of radiator, kPa (in. H
2
O)
0.125 (0.5)
Operation Requirements
Air Requirements
Radiator-cooled cooling air,
m
3
/min. (scfm) [
340 (12000)
Combustion air, m
3
/min. (cfm) 8.9 (314)
Heat rejected to ambient air:
Engine, kW (Btu/min.) 24.9 (1476)
Alternator, kW (Btu/min.) 15.7 (893)
[ Air density = 1.20 kg/m
3
(0.075 lbm/ft
3
)
Fuel Consumption]
Standby Rating
Natural Gas, m
3
/hr. (cfh) at % load
100% 55.7 (1965)
75% 43.3 (1529)
50% 31.2 (1102)
25% 19.5 (688)
0% 8.1 (286)
LPG, m
3
/hr. (cfh) at % load
100% 20.2 (713)
75% 15.5 (547)
50% 11.3 (399)
25% 7.2 (254)
0% 4.6 (164)
] Nominal fuel rating: Natural gas, 37 MJ/m
3
(1000 Btu/ft
3
)
LPG, 93 MJ/m
3
(2500 Btu/ft
3
)
LPG conversion factors:
8.58 ft.
3
=1lb.
0.535 m
3
=1kg.
36.39 ft.
3
= 1 gal.
Controller
APM402 Controller
Provides advanced control, system monitoring, and system diagnostics
for optimum performance and compatibility.
D Digital display and menu control provide easy local data access
D Measurements are selectable in metric or English units
D Remote communication thru a PC via network or
serial configuration
D Controller supports Modbusr protocol
D Integrated hybrid voltage regulator with 0.5% regulation
D Built-in alternator thermal overload protection
D NFPA 110 Level 1 capability
Refer to G6-161 for additional controller features and accessories.
Sound Enclosure
D Sound level (8 point logarithmic average) at 7 m (23 ft.) with full load:
73 dB(A).
D Sound level compared to competitor ratings with no load: 70 dB(A).*
D Sound attenuating enclosure uses acoustic insulation that meets
UL 94 HF1 flammability classification and repels moisture absorption.
D Vertical air inlet and outlet discharge with 90 degree bends to redirect
air and reduce noise.
D Internal-mounted critical silencer and flexible exhaust connector.
D Skid-mounted, steel (standard) or aluminum (optional) construction
with hinged doors.
D Fade-, scratch-, and corrosion-resistant Kohlerr Cashmere Power
Armort textured e-coat paint.
D Lockable, flush-mounted door latches.
D Certified to withstand 241 kph (150 mph) wind load rating (aluminum
enclosures only).
* Lowest of 8 points measured around the generator. Sound levels at
other points around generator may be higher depending on installation
parameters.