RXT 100A / 240V Outdoor Transfer Switch Specifications

G11-140 (Model RXT Automatic Transfer Switch) 4/16d Page 5
WCR Ratings with Specific Manufacturer’s Molded-Case Circuit Breakers
Switch
Rating,
Amps
Voltage,
max.
Number
of Poles/
Phases
WCR, RMS
Symmetrical
Amps
Manufacturer Type or Class
Maximum
Size, Amps
300
400
240
2 pole/
1 phase
35,000
ABB T5, T6 600
Eaton
CHKD, CKD, DK, HKD, K D, KDB, KDC,
LA TRIPAC, LCL
400
CHLD, CLD, CLDC, HLD, LD, LDB, LDC 600
HMDL, MDL, NB TRI--PAC 800
General Electric FGH, FGL, FGN, FGP, SGHA 600
Siemens
CJD6, HHJD6, HHJXD6, HJD6, HJGA, HJXD6,
JD6, JXD2, JXD6, SCJD6, SHJD6, SJD6
400
CLD, HHLD, HHLXD, HLD, HLGA, HLXD, LD,
LLGA, LXD, NLGA, SCLD, SHLD, SLD
600
CMD, HLMD, HLMXD, HMD, HMG, HMXD, LMD,
LMG, LMXD, MD, MXD, NMG, SCMD, SHMD,
SMD
800
Square D
LA, LC, LE, LH, LI, LX, LXI 400
DG,DJ,DL,LC,LE,LI,LX,LXI 600
Merlin Gerin
CJ400H, CJ400L, CJ400N 400
CJ600H, CJ600N 600
3 pole/
3 phase
35,000 Any Breaker Any Breaker (0.017 seconds max.) 600
50,000 Eaton LD 600
400 480
3 pole/
3 phase
4 pole/
3 phase
50,000
Eaton
HJD, JDC, JGC, JGH, JGU, JGX 250
CHLD4, CLD, HLD4, CLDC, LDC, KDC, HKD,
CHMDL4, CMDL4
400
CHLD6, HDL6, CHMDL6, CMDL6, CLDC, CLD6,
LDC6, CLDC6
600
CHMDL8, HMDL8, MDL8, CMDL8 800
ITE/Siemens CFD6, HFD6, HFXD6, HHFD6, HHFXD6 250
General Electric
SFL, SFP 250
FGL, FGP 600
Schneider
LJ, LL, LR 600