Product Manual

TP-6804 6/15 59Section 4 DC2 Controller Operation
4.7 Maintenance Timer
The maintenance timer keeps track of the time until the
next recommended maintenance according to the
maintenance schedule for the 14 kW or 20 kW generator
set. Reset the maintenance timer after changing the oil
and performing the other maintenance tasks
recommended in Section 5.
To reset the maintenance timer:
1. Press and hold the OFF and AUTO buttons
together until Maintenance Timer Reset is
displayed.
2. Release the OFF and AUTO buttons.
4.8 OnCue Password
For the initial OnCuer Plus setup, you will be required to
reset the OnCue password on the DC2 controller, and
then enter it into the OnCue Plus application. To reset
the password, follow the instructions below.
Note: Use the OnCue password shown on the
controller display for OnCue or OnCue Plus
applications.
1. Press the OFF button and verify that the generator
set is not running.
2. Press and hold the Exercise button until Press
Again to Reset OnCue PW is displayed.
3. Release the Exercise button and press it again
within 5 seconds.
Note: If the Exercise button is not pressed within 5
seconds, the controller exits the password
reset mode.
4. The genset serial number and new password (PW)
will be displayed for 10 seconds. Record the
password for entry into the OnCue Plus
application.