1.3 Location and Mounting
1.3.1 Lo cation Factors
The manufacturer recommends mounting the generator
set on concrete at ground level. For installations
suspended above ground level, including roof
installations, weight considerations are especially
important. The building engineer must determine
whether the structure can support the weight of the
generator set.
The location of the generator set must:
D Support the weight of the generator set and related
equipment such as batteries, radiators, and mounting
pad(s). Keep in mind that the mounting pad weight
may exceed the weight of the generator set.
D Meet applicable fire rating and other national, state,
and local codes and standards.
D Minimize the risk that people will come into contact
with hot generator set surfaces.
D Position the generator set over a noncombustible
surface. DO NOT allow accumulation of combustible
materials under or around the generator set.
D Permit vibration isolation to reduce noise and prevent
damage.
D Not be subject to flooding.
D Allow safe expulsion of exhaust.
D Provide clearance for cooling air flow and access for
service. See Figure 1-5 and the dimension drawings
in Section 4 for required clearances from obstructions
and combustible materials.
D Minimize the risk of public or unauthorized access.
Notice
DO NOT locate the generator set near patios,
decks, play areas, or animal shelters. Keep items
such as lawn furniture, toys, sports equipment,
and all combustible materials away from the
generator set exhaust outlet.
Remind family members, children, and visitors to
use caution near the generator set. Generator sets
connected to automatic transfer switches start
automatically during exercise periods and power
outages. Some generator set components
become hot when the generator set is running and
remain hot for a time after the generator set shuts
down.
SERVICE SIDE
GM91044-- MA2
Figure 1-5 Air Intake and Exhaust
1.3.2 Mounting Surface
Install the generator set on a single, level concrete
mounting pad. This method provides maximum stability
and ensures correct cooling air flow through the
generator set. The recommended mounting pad
dimensions are shown in the dimension drawings in
Section 4.
Refer to the generator set dimension drawings for
conduit and fuel-line placement (See Figure 4-4).
1.3.3 Vibration Isolation
The generator set is equipped with neoprene vibration
isolators. Connections between the generator set or its
mounting base and any conduits or fuel lines must
include flexible sections to prevent breakage and to
isolate vibration.