Install Manual

TP-6906 6/1420 Section 1 Installation Instructions
1.4.6 Connect AC and DC Wiring
Note: Have a licensed electrician make the following
electrical connections. All connections must
comply with state and local codes.
Size the wire according to the length of run and 115% of
the circuit current (amperage) based on 75_Cwire
rating or less as directed by the National Electrical
Coder (NEC) in ANSI/NFPA 70. See Section 1.4.1 for
additional information about wire selection.
The generator set is equipped with a field-connection
terminal block located in the access area below the
junction box. Leads have been factory-installed from the
junction box to the terminal block for easy field wiring.
See Figure 1-10. Make all AC and DC customer
connections inside the customer connection box. Do not
remove the upper panel or make connections inside the
upper area of the junction box. Refer to the wiring
diagrams in Section 4.
1. Access panel (remove to access connections)
2. Upper panel
3. Neutral lug
4. Load lead connections to line circuit breaker
5. Ethernet cable connection for OnCue Plus
6. G round (GRD) lug, 120VAC (utility power) connection
7. 120VAC (utility power) connection leads
8. Installer to punch access openings
9. Ground (GRD) lug, low voltage connection
10. Low voltage connection terminal block
11. Customer connection box
12. Terminal Ground (GRD) lug
13. Load lead access opening
1
Connection details
Access panel removed.
12
3
10
4
13
5
7
8
9
6
2
11
Figure 1-10 Generator Set Connections