Install Manual

TP-6906 6/14 27Section 1 Installation Instructions
RXT
3
COM
PWR
B
A
4
PIM
LCM
COM
PWR
COM
PWR
B
A
B
A
COM
PWR
B
A
COM
PWR
B
A
1. Customer connection terminal block. See Figure 1-10 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable (one pair)
4. Connect shields together as shown.
5. 12 AWG or 14 AWG leads for PWR and COM
6. Leave one end of each cable shield disconnected at the last device.
1
2
6
5
Note: See Section 1.4.8, Cable Specifications.
Generator Set
COM
PWR
B
A
GND
RBUS
12VDC
Figure 1-15 Accessory Module Connections with 12--14 AWG Power Leads (one cable run with three modules
shown)